Enviro-LOGO

MK-S

• Same mounting and internal wiring as the previous Super MK Relays

• Built-in mechanical indicator enables checking contact operation.

• Two modes can be used to check circuits for models with latching lever.

• Nameplate provided on models with latching lever.

• All materials are RoHS compliant.

• UL and IEC (TÜV) certification.

Ratings

Coil Ratings

 

Rated voltage Rated current Coil
resistance
Must operate
voltage
Must release
voltage
Max. voltage Power
consumption
50 Hz 60 Hz
AC 6 V 443 mA 385 mA 3.1 Ω 80% max. of
rated voltage
30% min. of rated
voltage at 60 Hz
25% min. of rated
voltage at 50 Hz
110% of rated
voltage
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
12 V 221 mA 193 mA 13.7 Ω
24 V 110 mA 96.3 mA 48.4 Ω
100 V 26.6 mA 23.1 mA 760 Ω
110 V 24.2 mA 21.0 mA 932 Ω
200 V 13.3 mA 11.6 mA 3,160 Ω
220 V 12.1 mA 10.5 mA 3,550 Ω
230 V 10.0 mA 11.5 mA 4,250 Ω
240 V 11.0 mA 9.6 mA 4,480 Ω
DC 6 V 224 mA 26.7 Ω 15% min. of rated
voltage
Approx. 1.4 W
12 V 112 mA 107 Ω
24 V 55.8 mA 430 Ω
48 V 28.1 mA 1,710 Ω
100 V 13.5 mA 7,390 Ω
110 V 12.3 mA 8,960 Ω
125 V 10.8 mA 11,576 Ω

 

 

Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20%
for AC rated current and ±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.
4. For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.

 

Contact Ratings

 

Load Resistive load (cosΦ = 1) Inductive load (cosΦ = 0.4)
Contact mechanism Single
Contact material AgSnIn
Rated load NO 10 A, 250 VAC
10A, 30 VDC
7 A, 250 VAC
NC 5 A, 250 VAC
5 A, 30 VDC
Rated carry current 10 A
Max. switching voltage 250 VAC, 250 VDC
Max. switching current 10 A
Max. switching power NO 2,500 VA/300 W
NC 1,250 VA/150 W

 

Characteristics

 

Contact resistance 100 mΩ max.
Operate time AC: 20 ms max.
DC: 30 ms max.
Release time 20 ms max. (40 ms max. for built-in Diode Relays)
Max. operating frequency Mechanical: 18,000 operations/h
Electrical: 1,800 operations/h (under rated load)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,500 VAC 50/60 Hz for 1 min between coil and contacts
1,000 VAC 50/60 Hz for 1 min between contacts of same polarity and terminals of the
same polarity
2,500 VAC 50/60 Hz for 1 min between current-carrying parts, non-current-carrying
parts, and opposite polarity
Insulation method Basic insulation
Impulse withstand voltage 4.5 kV between coil and contacts (with 1.2 × 50 μs impulse wave)
3.0 kV between contacts of different polarity (with 1.2 × 50 μs impulse wave)
Pollution degree 3
Rated insulation voltage 250 V
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Shock resistance Destruction: 1,000 m/s2 (approx. 100 G)
Malfunction: 100 m/s2 (approx. 10 G)
Endurance Mechanical: 5,000,000 operations min. (at 18,000 operations/h under rated load)
Electrical: 100,000 operations h. (at 1,800 operations/h under rated load)
Failure rate P level
(reference value)
10 mA at 1 VDC
Ambient temperature Operating: -40 to 60°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 90 g

 

 

Note: 1. The values given above are initial values.
2. P level: λ60 = 0.1 × 10-6/operation
3. Ambient temperature of models with LED indicator is −25 to 60°C.

 

Approved Standards

UL508 (File No. E41515)

MK-S Specifications 8

 

Coil ratings Contact ratings Operations
6 to 110 VDC
6 to 240 VAC
N.O. contact 10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C. contact 10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000

 

CSA Standard: CSA C22.2 No. 14 (File No. LR35535)

MK-S Specifications 9

 

Coil ratings Number of Poles Contact ratings Operations
6 to 125 VDC
6 to 240 VAC
2 10 A, 250 V AC (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC (General Use)
100,000
3 10 A, 250 V AC (Resistive) Same Polarity
10 A, 30 V DC (Resistive) Same Polarity
7 A, 250 V AC (General Use) Same Polarity
100,000

 

IEC Standard/TÜV Certification: IEC61810-1 (Certification No. R50104853)

MK-S Specifications 10

 

Coil ratings Contact ratings Operations
6, 12, 24, 48, 100, 110 VDC
6, 12, 24, 100, 110, 200, 220, 240 VAC
N.O. contact 10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C. contact 5 A, 250 V AC 50/60 Hz (Resistive)
5 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000