The H7CC series improves overall user experience through better visual feedback and operation, user interface and predictive remaining lifetime of counter.
Item | H7CC-A8/-A11[] | H7CC-A[] | H7CC-AW[]/AU[] | |
---|---|---|---|---|
Classification | Preset counter | Preset counter/ tachometer | ||
Configuration | 1-stage preset counter, 1-stage preset counter with total counter (selectable) *1 | 1-stage/2-stage preset counter, total and preset counter *1, batch counter, dual counter, twin counter, and tachometer (selectable) |
||
Ratings | Power supply voltage *2 |
• 100 to 240 VAC, 50/60 Hz • 24 VAC, 50/60 Hz or 12 to 48 VDC |
||
Operating voltage fluctuation range |
85% to 110% of rated supply voltage (12 to 48 VDC: 90% to 110%) | |||
Power consumption |
Approx. 6.8 VA at 100 to 240 VAC, Approx. 5.5 VA/3.3 W at 24 VAC/12 to 48 VDC, |
|||
Mounting method | Flush mounting or surface mounting | Flush mounting | ||
External connections | 8-pin/ 11-pin socket | Screw terminals | ||
Degree of protection | IEC IP66 for panel surface only and only when Y92S-P6 Waterproof Packing is used. | |||
Input signals | CP1, CP2, reset, and total reset *4 | CP1, CP2, reset 1, and reset 2 | ||
Counter | Maximum counting speed |
30 Hz (minimum pulse width: 16.7 ms) or 10 kHz (minimum pulse width: 0.05 ms) (selectable) (ON/OFF ratio 1:1) *Common setting for CP1 and CP2 |
||
Input mode |
Increment (UP), decrement (DOWN), increment/decrement (UP/DOWN A (command input), UP/DOWN B (individual inputs), or UP/DOWN C (quadrature inputs)), UP/DOWN D (command input), UP/DOWN E (individual inputs), UP/DOWN E (quadrature inputs) | |||
Output mode |
N, F, C, R, K-1, P, Q, A, K-2, D, and L. | N, F, C, R, K-1, P, Q, A, K-2, D, L, and H. | ||
One-shot out put time |
0.01 to 99.99 s | |||
Reset system |
External (minimum reset signal width: 1 ms or 20 ms, selectable), manual, and automatic reset (internal according to C, R, P, and Q mode operation) | |||
Tachometer | Refer to the tachometer function ratings. | |||
Prescaling function | Yes (0.001 to 99.999) | |||
Decimal point adjustment | Yes (right most 3 digits) | |||
Sensor waiting time | 290 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.) | |||
Input method | No-voltage (NPN) input/voltage (PNP) input (switchable) No-voltage inputs: ON impedance: 1 kΩ max. (Leakage current: 12 mA at 0 Ω) ON residual voltage: 3 V max. OFF impedance: 100 kΩ min. Voltage input: High (logic) level: 4.5 to 30 VDC Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ) |
|||
External power supply | 12 VDC (±10%), 100 mA (except for H7CC-A8[] models) Refer to Precautions for Correct Use on Catalog for details. | |||
Control output | • Contact output: 3 A at 250 VAC/30 VDC, resistive load (cosφ=1), Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value) • Transistor output: NPN open collector, 100 mA at 30 VDC, Residual voltage: 1.5 VDC max. (approx. 1 V), Leakage current: 0.1 mA max. |
|||
Display *3 | 7-segment, negative transmissive LCD Character height Count value: 10 mm (white) Set value: 6 mm (green) |
|||
Digits | 6 digits -99999 to 999999 (-5 digits to +6 digits) |
6 digits -99999 to 999999 (-5 digits to +6 digits), tachometer: 0 to 999999 |
||
Memory backup | Non-volatile memory (overwrites: 100,000 times min.) that can store data for 10 years min. | |||
Operating temperature range | -10 to 55°C (-10 to 50°C if Counter/Tachometers are mounted side by side) (with no icing or condensation) | |||
Storage temperature range | -25 to 70°C (with no icing or condensation) | |||
Operating humidity range | 25% to 85% | |||
Case color | Black (N1.5) | |||
Attachments | — | Flush mounting adapter, waterproof packing, terminal cover |
*1. 1-stage preset counter and total counter functionality.
*2. Do not use the output from an inverter as the power supply.The ripple must be 20% maximum for DC power.
*3. The display is lit only when the power is ON. Nothing is displayed when power is OFF.
*4. Only reset input is performed in the H7CC-A8[], and the total count is also reset simultaneously.
Item | H7CC-A8[] H7CC-A11[] H7CC-A[] |
H7CC-AW[]/AU[] | |||
---|---|---|---|---|---|
Input mode | No tachometer functionality |
Selectable from 1 inputs, independent measurements for 2 inputs, differential input for 2 inputs, absolute ratio for 2 inputs, and error ratio for 2 inputs. |
|||
Pulse measurement method |
Periodic measurement | Pulse width measurement | |||
Maximum counting speed |
30 Hz (minimum pulse width: 16.7 ms) |
1-input mode: 10 kHz (minimum pulse width: 0.05 ms) Other modes: 5 kHz (minimum pulse width: 0.1 ms) |
30 Hz (minimum pulse width: 16.7 ms) |
1-input mode: 10 kHz (minimum pulse width: 0.05 ms) Other modes: 5 kHz (minimum pulse width: 0.1 ms) |
|
Minimum input signal width |
— | — | 30 ms * | 1-input mode: 0.2 ms Other modes: 0.4 ms* |
|
Measuring ranges | 0.001 to 30.00 Hz | 1-input mode: 0.001 to 10 kHz, Other modes: 0.01 to 5 kHz |
0.030 to 999999 s | 1-input mode: 0.0002 to 999999 s Other modes: 0.0004 to 999999 s |
|
Sampling period | 200 ms min. | 200 ms min. or continuous selectable (minimum interval of 10 ms) |
Continuous (minimum interval of 10 ms) | ||
Measuring accuracy | ±0.1% FS ±1 digit max. (at 23 ±5°C) | ||||
Output mode | Input mode: Not 2-input independent measurement: HI-LO, AREA, HI-HI, LO-LO 2-input independent measurement: HI-HI, LO-LO |
||||
Auto-zero time | 0.1 to 999.9s | ||||
Startup time | 0.0 to 99.9s | ||||
Averaging | Simple averaging/moving averaging selectable, Processing: OFF, 2, 4, 8, or 16 times | ||||
Hold input | Minimum input signal width: 20 ms |
* An input OFF time of at least 20 ms is required.
Insulation resistance | 100 MΩ min. (at 500 VDC) between current-carrying terminals and exposed non-current-carrying metal parts, and between non-continuous contacts | |
---|---|---|
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts 2,000 VAC, 50/60 Hz for 1 min between power supply and input circuit for all models except H7CC-[]D[] (1,500 VAC for 24 VAC/12 to 48 VDC) 1,500 VAC (for H7CC-[]SD[]), 50/60 Hz for 1 min between control output, power supply, and input circuit (2,000 VACfor models other than H7CC-[]SD[]) 1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts |
|
Impulse withstand voltage | 6.0 kV between power terminals (1.0 kV for models with 24 VAC/12 to 48 VDC) 6.0 kV between current-carrying terminals and exposed non-current-carrying metal parts (1.5 kV for models with 24 VAC/12 to 48 VDC) |
|
Static immunity | Malfunction: 8 kV Destruction: 15 kV |
|
Vibration resistance |
Destruction | 10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each |
Malfunction | 10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each | |
Shock resistance |
Destruction | 300 m/s2 each in three directions |
Malfunction | 100 m/s2 each in three directions | |
Life expectancy | Mechanical: 10,000,000 operations min. Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load, ambient temperature condition: 23°C) * |
|
Weight | Approx. 120 g (Counter only) |
* Refer to the Life-test Curve.
A current of 0.15 A max. can be switched at 125 VDC (cosφ=1) and current of 0.1 A max. can be switched if L/R=7 ms. In both cases, a life of 100,000 operations can be expected.
Approved safety standards |
cULus (or cURus): UL508/CSA C22.2 No. 14 *1 EN 61010-1 (IEC 61010-1): Pollution degree 2/overvoltage category II EAC RCM B300 PILOT DUTY 1/4 HP 120 VAC, 1/3 HP, 240 VAC, 3 A, 250 VAC/30 VDC resistive load VDE0106/part100 |
---|---|
EMC | (EMI) EN61326-1 *2 Emission Enclosure: EN 55011 Group 1 class A Emission AC mains: EN 55011 Group 1 class A (EMS) EN61326-1 *2 Immunity ESD: EN 61000-4-2: 4 kV contact discharge; 8 kV air discharge Immunity RF-interference: EN 61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) 3 V/m (Amplitude-modulated, 1.4 G to 2 GHz) 1 V/m (Amplitude-modulated, 2 G to 2.7 GHz) 10 V/m (Pulse-modulated, 900 MHz ±5 MHz) Immunity Conducted Disturbance: EN 61000-4-6: 10 V (0.15 to 80 MHz) Immunity Burst: EN 61000-4-4: 2 kV power-line; 1 kV I/O signal-line Immunity Surge: EN 61000-4-5: 1 kV line to lines (power and output lines); 2 kV line to ground (power and output lines) Immunity Voltage Dip/Interruption: EN 61000-4-11: Voltage Dip 1 cycle, 100% (rated voltage) 10/12 cycle 60% (rated voltage) 25/30 cycle 30% (rated voltage) Interruption 250/300 cycle 100% (rated voltage) |
*1. The following safety standards apply to models with sockets (H7CC-A11[]/H7CC-A8[]).
cUL (Listing): Applicable when an OMRON P2CF(-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
*2. Industrial electromagnetic environment (EN/IEC 61326-1Table 2)
Inputs | CP1, CP2 | (1) In general (except for Dual Counter Mode) • Reads counting signals. • Increment, decrement, increment/decrement (command/individual/quadrature) inputs accepted. (2) When used as a dual counter or twin counter • Reads CP1 count signals with CP1 input and CP2 count signals with CP2 input. • Increment signals can be input. |
---|---|---|
Reset/reset 1 | (1) In general (except for Dual Counter Mode) • Resets present value and outputs (OUT2 when using the batch counter) *2. • Counting cannot be performed during reset/reset 1 input. • Reset indicator is lit while reset input is ON. (2) When used as a dual counter or twin counter. • Resets the CP1 present value (to 0). • Counting for CP1 input cannot be performed while the reset 1 input is ON. • The reset indicator is lit while the reset 1 input is ON. |
|
Total reset or reset 2 |
The reset function depends on the selected configuration *3. | |
Outputs | OUT1, OUT2 | Outputs signals according to the specified output mode when a set value is reached. |
*1. For information on operation of I/O functions, refer to Catalog.
*2. In increment mode or increment/decrement mode, the present value returns to 0; in decrement mode, the present value returns to the set value with 1-stage models, and returns to set value 2 with 2-stage models.
*3. Reset operates as described in the following table. (The reset indicator will not be lit.)
Configuration | Reset operation |
---|---|
1-stage/2-stage preset counter |
Does not operate (not used). |
Total and preset counter | • Resets the total count value. • The total count value is held at 0 while the total reset input is ON. |
Batch counter | • Resets the batch count value and batch output (OUT1). • The batch count value is held at 0 while the reset 2 input is ON. |
Dual counter | • Resets the CP2 present value. • Counting for CP2 input cannot be performed while the reset 2 input is ON. |
Twin counter | • Resets the CP2 present value. |
• The following table shows the delay from when the reset signal is input until the output is turned OFF. (Reference values)
Minimum reset signal width | Output delay time | |
---|---|---|
Relay output | Transistor output | |
1 ms | 3.7 to 6.6 ms | 0.58 to 0.78 ms |
20 ms | 17.0 to 19.8 ms | 13.7 to 17.2 ms |
Inputs | CP1, CP2 | Reads counting signals. (The CP2 input can be used when the input mode is not 1-input mode.) |
---|---|---|
Reset 1/reset 2 | • Holds the measurement value and outputs. (The reset 2 input can be used when the input mode is 2-input independent measurement.) • Functions as a hold input. The measurement value (displayed value) and the outputs are held while the RST Key on the front panel is pressed. • The hold indicator is lit when the value is being hold. |
|
Outputs | OUT1, OUT2 | Outputs signals according to the specified output mode when a set value is reached. |