Indication accuracy
(when mounted
individually, ambient
temperature of 23°C) |
Thermocouple: (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max. *1
Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is
greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max. |
Simple transfer output
accuracy |
±0.3% FS max.*2 |
Influence of
temperature *3 |
Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is
greater) ±1 digit max.
Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit
max. *4
Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1
digit max.
Analog input: ±1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max. |
Influence of voltage *3 |
Influence of EMS.
(at EN 61326-1) |
Installation influence
(E5DC only) |
R, S, B, W, or PLII thermocouple: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *4 |
Input sampling period |
50 ms |
Hysteresis |
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) |
Proportional band (P) |
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) |
Integral time (I) |
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 |
Derivative time (D) |
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 |
Proportional band (P)
for cooling |
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) |
Integral time (I) for
cooling |
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 |
Derivative time (D) for
cooling |
0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5 |
Control period |
0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) |
Manual reset value |
0.0% to 100.0% (in units of 0.1%) |
Alarm setting range |
-1,999 to 9,999 (decimal point position depends on input type) |
Influence of signal
source resistance |
Thermocouple: 0.1°C/Ω max. (100 Ω max.),
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) |
Insulation resistance |
20 MΩ min. (at 500 VDC) |
Dielectric strength |
3,000 VAC, 50/60 Hz for 1 min between terminals of different charge |
Vibration |
Malfunction |
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions |
Resistance |
10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions |
Shock |
Malfunction |
100 m/s2, 3 times each in X, Y, and Z directions |
Resistance |
300 m/s2, 3 times each in X, Y, and Z directions |
Weight |
Main unit: Approx. 80 g, Models with Screw Terminal Unit: Approx. 40 g,
Models with Push-In Plus Terminal Unit: Approx. 40 g |
Degree of protection |
Main unit: IP20, Terminal unit: IP00 |
Memory protection |
Non-volatile memory (number of writes: 1,000,000 times) |
Setup Tool |
CX-Thermo version 4.6 or higher |
Setup Tool port |
E5DC/E5DC-B bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to
connect a USB port on the computer. *6
E5DC/E5DC-B front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E
Conversion Cable are used together to connect a USB port on the computer. *6 |
Standards |
Approved
standards |
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark)
(Some models only.) *7, Lloyd’s standards (E5DC only) *8, EAC |
Conformed
standards |
EN 61010-1 (IEC 61010-1), RCM |
EMC |
EMI: EN61326-1 *9
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326-1 *9
ESD Immunity: EN61000-4-2
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conducted Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11 |