Power supply voltage |
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC |
Operating voltage range |
85% to 110% of rated supply voltage |
Power consumption |
Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at
24 VAC or 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W
max. at 24 VDC |
Sensor input |
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to
260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to
the E5CC-U only for those manufactured in May 2014 or later.) |
Input impedance |
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB-N/THB-N.) |
Control method |
ON/OFF control or 2-PID control (with auto-tuning) |
Control
output |
Relay output |
E5CC/E5CC-B:
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA (reference value)
E5CC-U:
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA (reference value) |
Voltage output
(for driving SSR) |
Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit
protection circuit |
Linear current
output |
4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 |
Auxiliary
output |
Number of
outputs |
E5CC: 3
E5CC-B: 2
E5CC-U: 1 or 2 (depends on model) |
Output
specifications |
SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U
models with 2
outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models
with 3
outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load:
10 mA at 5 V (reference value) |
Event
input *1 |
Number of inputs |
E5CC: 2 or 4 (depends on model)
E5CC-B: 2 (depends on model) |
External contact
input
specifications |
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. |
Current flow: Approx. 7 mA per contact |
Transfer
output *1 |
Number of
outputs |
1 (only on models with a transfer output) |
Output
specifications |
Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000 |
Setting method |
Digital setting using front panel keys |
Remote SP input *1 *2 |
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) |
Indication method |
11-segment digital display and individual indicators
Character height: PV: 15.2 mm, SV: 7.1 mm |
Multi SP *3 |
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key
operations, or serial communications. |
Bank switching |
None |
Other functions |
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm
functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100%
AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop,
protection functions, extraction of square root, MV change rate limit, logic operations,
temperature status display, simple programming, moving average of input value, and
display brightness setting |
Ambient operating
temperature |
-10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with
standard mounting (with no condensation or icing) |
Ambient operating humidity |
25% to 85% |
Storage temperature |
-25 to 65°C (with no condensation or icing) |
Altitude |
2,000 m max. |
Recommended fuse |
T2A, 250 VAC, time-lag, low-breaking capacity |
Installation environment |
Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |