• Specify the operation days.
(However, you can set only one pattern of operation days and specified days.)
• Up to 12 ON/OFF operations (24 for pulse-output operation).
• Special holidays can be handled easily with the holiday setting function.
• Adjustments for sudden schedule changes can be made easily using output override and automatic return operation.
• The operation program can be checked easily with the program check function.
• Enables pulse output operation and summer time setting.
• Incorporates finger-safe terminals.
• Conforms to UL, CSA, and CE marking.
• Meets a variety of mounting requirements: flush mounting, surface mounting, and DIN track mounting.
Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power consumption | Approx. 2.4 VA at 264 VAC |
Control outputs | Contact output: SPST-NO, 15 A at 250 VAC, resistive load, 10 A at 24 VDC, resistive load Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value) |
NEMA A300 Pilot Duty, 1/3 HP at 120 VAC | |
External connections | Screw terminals (M3.5 screw) |
Terminal screw tightening torque |
0.98 to 1.17 Nm |
Accuracy of operating time |
±0.01% ±0.05 s max. *1 |
---|---|
Setting error | |
Influence of voltage | |
Influence of temperature |
|
Influence of EMS. (at EN61326-1) |
|
Time accuracy | ±15 s per month (at 25°C) |
Memory protection | Continuous use: 5 years min. (at 25°C); Power-interruption rate of 50%: 10 years min. (at 25°C) *2 (lithium battery) |
Insulation resistance | 100 MΩ min. (between current-carrying terminals and exposed non-current-carrying metal parts, between operating power supply circuit and control output circuit and between non- continuous contacts) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non- current-carrying metal parts and between operating power supply circuit and control output circuit) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Noise immunity | 1.5 kV (between power terminals) Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
Vibration resistance | Destruction:10 to 55 Hz with 0.375-mm single amplitude, four cycles each in three directions (8 minutes per cycle) Malfunction:10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions |
Shock resistance | Destruction:300 m/s2 3 times each in 6 directions Malfunction:100 m/s2 3 times each in 6 directions |
Ambient temperature | Operating: -10°C to 55°C (with no icing) Storage: -25°C to 65°C (with no icing) |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | Mechanical (at 20°C): 100,000 operations min. Electrical (at 20°C): 50,000 operations min. (15 A, 250 VAC, resistive load) 50,000 operations min. (1 HP, 250 VAC, motor load) 50,000 operations min. (10 A, 250 VAC, inductive load (cosφ = 0.7)) 50,000 operations min. (100 W, 100 VAC, lamp load) 10,000 operations min. (300 W, 100 VAC, lamp load) |
Approved safety standards |
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II) Conforms to VDE0106/P100 (finger protection). Conforms to Electrical Appliance and Material Safety Law (for Japan) |
EMC | (EMI) EN61326-1 *3 Emission Enclosure: EN55011 Group 1 class A Emission AC mains: EN55011 Group 1 class A (EMS) EN61326-1 *3 Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3) Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz, 1.4 to 2 GHz) (level 3) Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (according to EN61000-6-2) Immunity Burst: EN61000-4-4: 2 kV power-line (level 3); 1 kV I/O signal-line (level 4) Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 2); 2 kV line to ground (power and output lines) (level 3) Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage) Immunity Magnetic Power Field: EN61000-4-8: 30 A/m |
Case color | Light gray (Munsell 5Y7/1) |
Weight | H5F-B: approx. 115 g; H5F-KB: approx. 160 g; H5F-FB: approx. 130 g |