Easy Programming with Large Display and InteractiveFunctions.
• Easy operation with five keys.
• Up to 24 steps of ON/OFF operations can be set.
• Power supply freely selectable from 100 to 240 VAC.
• Memory protection during power failure for up to 10 years.
• Certified for UL and CSA safety standards.
• The same setting can be used for multiple-day operation andtimer operation.
Rated time | Time setting range | Time division |
---|---|---|
24 hrs x 7 days | 00:00 to 23:59 | 1 min |
Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power consumption | Approx. 4 VA at 240 VAC |
Control outputs | 15 A at 250 VAC, resistive load at 50°C 12 A at 250 VAC, resistive load at 55°C Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value) |
Accuracy of operating time | ±0.01% ±0.05 s max. *1 |
---|---|
Setting error | |
Influence of voltage | |
Influence of temperature | |
Time accuracy | ±15 s per month (at 25°C) |
Insulation resistance | 100 MΩ min. |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non- current-carrying metal parts and between control power supply circuit and contact control output circuits) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Vibration resistance | Destruction: 10 to 55 Hz with 0.75-mm double amplitude Malfunction: 10 to 55 Hz with 0.5-mm double amplitude |
Shock resistance | Destruction: 300 m/s2 (approx. 30G) Malfunction: 100 m/s2 (approx. 10G) |
Ambient temperature | Operating: -10°C to 55°C |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | 100,000 operations min. (15 A at 250 VAC, resistive load) |
Degree of protection | IP-40 (Rear case: IP-20, Terminals: IP-00) |
Weight | Approx. 350 g |
Approved standards | UL917 CSA 22.2 No.14 Conforms to Electrical Appliance and Material Safety Law (for Japan) CCC: GB/T 14048.5 Pollution degree 2, Overvoltage category II *2 |
Recommended fuse | 021702.5 (250 VAC, 15 A), manufactured by Littelfuse |
---|---|
Rated operating voltage Ue Rated operating current Ie |
AC-15: Ue: 250 VAC, Ie: 10 A DC-13: Ue: 125 VAC, Ie: 15 A |
Rated insulation voltage | 250 V |
Rated impulse withstand voltage (altitude: 2,000 m max.) |
2.5 kV (at 240 VAC) |
Conditional short-circuit current | 1,000 A |