Daily Time Switch H5L

Categories , Tag

Easy Programming with Large Display and InteractiveFunctions.

• Easy operation with five keys.

• Up to 24 steps of ON/OFF operations can be set.

• Power supply freely selectable from 100 to 240 VAC.

• Memory protection during power failure for up to 10 years.

• Certified for UL and CSA safety standards.

• The same setting can be used for multiple-day operation andtimer operation.

Time Ranges

 

Rated time Time setting range Time division
24 hrs x 7 days 00:00 to 23:59 1 min

 

Ratings

 

Rated supply voltage 100 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power consumption Approx. 4 VA at 240 VAC
Control outputs 15 A at 250 VAC, resistive load at 50°C
12 A at 250 VAC, resistive load at 55°C
Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value)

 

Characteristics

 

Accuracy of operating time ±0.01% ±0.05 s max. *1
Setting error
Influence of voltage
Influence of temperature
Time accuracy ±15 s per month (at 25°C)
Insulation resistance 100 MΩ min.
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-
current-carrying metal parts and between control power supply circuit and contact
control output circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance Destruction: 300 m/s2 (approx. 30G)
Malfunction: 100 m/s2 (approx. 10G)
Ambient temperature Operating: -10°C to 55°C
Ambient humidity Operating: 35% to 85%
Life expectancy 100,000 operations min. (15 A at 250 VAC, resistive load)
Degree of protection IP-40 (Rear case: IP-20, Terminals: IP-00)
Weight Approx. 350 g
Approved standards UL917 CSA 22.2 No.14
Conforms to Electrical Appliance and Material Safety Law (for Japan)
CCC: GB/T 14048.5 Pollution degree 2, Overvoltage category II *2

 

 

*1. The overall error, which includes repeat accuracy, setting error, and variations due to changes in voltage and
temperature, is ±0.01% or ±0.05 s max. The accuracy of ±0.01% also indicates the error in the time interval of the set
time.
*2. CCC certification requirements.

 

 

Recommended fuse 021702.5 (250 VAC, 15 A), manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 10 A
DC-13: Ue: 125 VAC, Ie: 15 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.)
2.5 kV (at 240 VAC)
Conditional short-circuit current 1,000 A