Terminal Relay G6D-F4PU / G3DZ-F4PU, G6D-F4B / G3DZ-F4B

Category Tag

• Realized 5 A rating by optimal designs for wide variety of applications (Push-In Plus technology).

• Push-In Plus terminal enables work reduction and requires no retightening.

• Short Bars (order separately) ensure easy common wiring and crossover wiring to adjacent terminal relays.

• Double wire method enables branch wiring (Push-In Plus technology)

• Each relay has independent coils and contacts for PLC output compatible (both NPN and PNP).

• Mechanical Relay models and power MOS FET relay models (for high frequency contact ratings) are available.

• LED operation indicator, diode for coil surge absorption, and tools for easy removal of relays are included as standard equipment.

• UL and CSA certification for standard models.
VDE certification for Screws terminal, TÜV certification for Push-In Plus terminal.
IP20 protection code for Push-In Plus models.

Ratings

Relay Specification

Coil Ratings (per G6D Relay)

 

Operation
coil rating
Rated current
(mA)
Coil resistance
(Ω)
Must operate
voltage (V)
Must release
voltage (V)
Max.
voltage (V)
Power
consumption (mW)
DC 12 18.7 720 70%
max.*
10%
min.
130% Approx. 200
24 10.5 2,880

 

Note:
1. Rated current and coil resistance were measured at a coil temperature of 23°C with a tolerance of ±20%.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum allowable voltage is the maximum value of the operating voltage for the relay coil operating power supply. There is no continuous allowance.
4. The rated current includes the terminal’s LED current.
* The must operate voltage is 75% or less of the rated voltage if the relay is mounted in the upside down.

Contact Ratings (per G6D Relay)

G6D-F4PU (Model with Push-In Plus technology)

 

Load Resistive load (cosφ = 1)
Rated load 5 A at 250 VAC, 5 A at 30 VDC
Rated carry current 5 A
Max. switching voltage 250 VAC, 30 VDC
Max. switching current 5 A
Max. switching capacity (reference value) 1,250 VA, 150 W

 

G6D-F4B (Model with Screw terminal)

 

Load Resistive load (cosφ = 1)
Rated load 3 A at 250 VAC, 3 A at 30 VDC
Rated carry current * 5 A
Max. switching voltage 250 VAC, 30 VDC
Max. switching current * 5 A
Max. switching capacity (reference value) * 1,250 VA, 150 W

 

* The specifications become 3 A, 750 VA, and 90 W when all four outputs are powered at the same time.

Characteristics

 

Model G6D-F4PU
(Model with Push-In Plus technology)
Relay output
Contact resistance *1 100 mΩ max.
Operate time *2 10 ms max.
Release time *2 10 ms max.
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric
strength
Between coil and
contacts
2,000 VAC, 50/60 Hz for 1 min
Between contacts
of the same polarity
750 VAC, 50/60 Hz for 1 min
Shock resistance voltage
(between coil and contacts)
4,000 V (1.2 × 50 μs)
Vibration re-
sistance
Destruction 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Shock
resistance
Destruction 500 m/s2
Malfunction 100 m/s2
Endurance Mechanical 20,000,000 operations min.
(switching frequency: 18,000 operations/hr)
Electrical *2 70,000 operations min.
(5 A at 250 VAC, resistive load)
70,000 operations min.
(5 A at 30 VDC, resistive load)
(at 1,800 switching frequencies/hr)
Failure rate P Level
(reference value *3)
10 mA at 5 VDC
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity 45% to 85%
LED color Yellow
Sealing IP20
Weight Approx. 95 g

 

Note: The data shown above are initial values.
*1. Measurement condition: 1 A at 5 VDC
*2. Ambient temperature condition: 23°C
*3. This value is measured at 120 switching frequencies/min.

 

Model G6D-F4B
(Model with Screw terminal)
Relay output
Contact resistance *1 100 mΩ max.
Operate time *2 10 ms max.
Release time *2 10 ms max.
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric
strength
Between coil and
contacts
2,000 VAC, 50/60 Hz for 1 min
Between contacts
of the same polarity
750 VAC, 50/60 Hz for 1 min
Shock resistance voltage
(between coil and contacts)
4,000 V (1.2 × 50 μs)
Vibration re-
sistance
Destruction 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Shock
resistance
Destruction 500 m/s2
Malfunction 100 m/s2
Endurance Mechanical 20,000,000 operations min.
(switching frequency: 18,000 operations/hr)
Electrical *2 200,000 operations min.
(3 A at 250 VAC, resistive load)
200,000 operations min.
(3 A at 30 VDC, resistive load)
(at 1,800 switching frequencies/hr)
Failure rate P Level
(reference value *3)
10 mA at 5 VDC
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity 45% to 85%
LED color Yellow
Sealing
Weight Approx. 65 g

 

Note: The data shown above are initial values.
*1. Measurement condition: 1 A at 5 VDC
*2. Ambient temperature condition: 23°C
*3. This value is measured at 120 switching frequencies/min.

Ratings

Power MOS FET Relay Specifications

Input (per G3DZ Power MOS FET Relay)

 

Rated
voltage
Operating
voltage
Must operate
voltage level
Must release
voltage level
Input
impedance
Rated
current
DC 12 9.6 to 14.4 VDC 9.6 VDC max. 1 VDC min. 2 kΩ ±20% 8.0 mA ±20%
24 19.2 to 28.8 VDC 19.2 VDC max. 4 kΩ ±20% 8.2 mA ±20%

 

Note: The rated current includes the terminal’s LED current.

Output (per G3DZ Power MOS FET Relay)

 

Rated operating
voltage
Load voltage
range
Load current Inrush current
resistance
5 to 240 VAC
5 to 100 VDC
3 to 264 VAC
3 to 125 VDC
100 μ to 0.3 A 6 A (10 ms)

 

Note: There is no output polarity for the G3DZ.

Characteristics

 

Model G3DZ-F4PU
(Model with Push-In Plus technology)
Power MOS FET relay output
Must operate time 10 ms max.
Release time 15 ms max.
Output ON-resistance 2.4 Ω max.
Leakage current at OFF state 10 μA max. (at 125 VDC)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength between I/O 2,000 VAC, 50/60 Hz for 1 min
Vibration resistance 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Shock resistance 500 m/s2
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity 45% to 85%
LED color Yellow
Sealing IP20
Weight Approx. 95 g

 

 

Model G3DZ-F4B
(Model with Screw terminal)
Power MOS FET relay output
Must operate time 10 ms max.
Release time 15 ms max.
Output ON-resistance 2.4 Ω max.
Leakage current at OFF state 10 μA max. (at 125 VDC)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength between I/O 2,000 VAC, 50/60 Hz for 1 min
Vibration resistance 10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Shock resistance 500 m/s2
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity 45% to 85%
LED color Yellow
Sealing
Weight Approx. 65 g

 

Ratings for Safety Standard Certification

The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.

G6D-F4PU/G3DZ-F4PU

UL-certified Models (File No. E41515)

 

Model Standard
number
Category Listed/
Recognized
Classification
Operating
coil ratings
Number
of poles
Contact ratings Operations
G6D-F4PU UL508 NRNT/7 Listed 12 VDC
24 VDC
4 Rated load voltage
250 VAC
30 VDC

Load Current, General
Use and Resistive
5 A

6,000
operations.
G3DZ-F4PU Rated load voltage
5-240 VAC
5-100 VDC

Load Current, General
Use and Resistive
0.3 A

P6DF-F4PU SWIV2 Recognized 5 A, 250 V

 

CSA-certified Models (File No. LR35535)

 

Model Standard number Class number Operating
coil ratings
Number
of poles
Contact ratings Operations
P6DF-F4PU C22.2 NO. 14 CLASS 3211 07 12 VDC
24 VDC
4 5 A, 250 V

 

TÜV Rheinland Certification (Certification No.R50429253)

 

Model Operating Coil ratings Number of poles Contact ratings Operations
G6D-F4PU 12 VDC
24 VDC
4 AC250 V, 5 A (Res.)
DC30 V, 5 A (Res.)
70,000 operations
70,000 operations

 

TÜV Rheinland Certification (Certification No.R50429249)

 

Model Operating Coil ratings Number of poles Contact ratings Operations
G3DZ-F4PU 12 VDC
24 VDC
4 AC5-240 V, 5 A (Res.)
DC5-100 V, 5 A (Res.)

 

TÜV Rheinland Certification (Certification No.50429224)

 

Model Operating Coil ratings Number of poles Contact ratings Operations
P6DF-F4PU 12 VDC
24 VDC
4 AC250 V, 5 A
DC100 V, 5 A

 

G6D-F4B/G3DZ-F4B

UL-certified Models (File No. E87929)

 

Model Standard
number
Category Listed/
Recognized
Classification
Operating
coil ratings
Number
of poles
Contact ratings Operations
G6D-F4B UL508 SWIV2 Recognized 12 VDC
24 VDC
4 Rated load voltage
250 VAC
30 VDC

Load Current
5 A, Resistive

6,000 operations.
G3DZ-F4B Rated load voltage
3-264 VAC
3-125 VDC

Load Current
0.3 A

 

CSA-certified Models (File No. LR35535)

 

Model Standard
number
Class number Operating
coil ratings
Number
of poles
Contact ratings Operations
G6D-F4B C22.2 NO. 14 CLASS 3211 07 12 VDC
24 VDC
4 Rated load voltage
250 VAC
30 VDC

Load Current
5 A, Resistive

G3DZ-F4B Rated load voltage
3-264 VAC
3-125 VDC

Load Current
0.3 A, Resistive

 

VDE Certification (Certification No.40017757)

 

Model Operating coil ratings Number of poles Contact ratings Operations
G6D-F4B 12 VDC
24 VDC
4 250 VAC, 3 A
24 VDC, 3 A

 

VDE Certification (Certification No.40046252)

 

Model Operating coil ratings Number of poles Contact ratings Operations
G3DZ-F4B 12 VDC
24 VDC
4 5-240 VAC, 0.3 A
5-100 VDC, 0.3 A

 

VDE Certification (Certification No.40046241)

 

Model Operating coil ratings Number of poles Contact ratings Operations
P6DF-F4B 12 VDC
24 VDC
4 250 VAC, 0.3 A