• Equipped with four G6B Mini-relays that are compact, highly sensitive, and highly resistant to dielectric surges, and that can switch 5 amps of power.
• Sealed plastic construction used for relays.
• Easy wiring with separated input/output terminals.
• Special P6B Mounting Socket used to facilitate maintenance (except for high-reliability models).
• UL and CSA certification for standard models (except for high-reliability models). VDE certification for G6B-4BND/47BND/48BND for 12/24 VDC.
• DIN Track mounting, and screw mounting models are available.
• SSR-equipped G3S4 models are also available.
| Rated voltage | 5 VDC | 12 VDC | 24 VDC |
|---|---|---|---|
| Rated current | 35.5 mA (43.4) | 19.1 mA | 10.7 mA (10.3) |
| Coil resistance | 125 Ω | 720 Ω | 2,880 Ω |
| Must operate voltage | 80% max. of rated voltage | ||
| Must release voltage | 10% min. of rated voltage | ||
| Max. voltage | 130% of rated voltage | ||
| Power consumption | Approx. 200 mW | ||
| Classification | G6B-4BND (standard), G6B-47BND (long-life) | G6B-48BND (high-reliability) | ||
|---|---|---|---|---|
| Load | Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4, L/R = 7 ms) |
Resistive load (cosφ = 1) |
Inductive load (cosφ = 0.4, L/R = 7 ms) |
| Rated load | 5 A at 250 VAC, 5 A at 30 VDC |
2 A at 250 VAC, 2 A at 30 VDC |
2 A at 250 VAC, 2 A at 30 VDC |
0.5 A at 250 VAC, 0.5 A at 30 VDC |
| Rated carry current | 5 A | 2 A | ||
| Max. switching voltage | 380 VAC, 125 VDC | |||
| Max. switching current | 5 A | 2 A | 2 A | 0.5 A |
| Max. switching power | 1,250 VA, 150 W | 500 VA, 60 W | 500 VA, 60 W | 125 VA, 15 W |
| Error rate (reference value) (see note) |
10 mA at 5 VDC | 1 mA at 1 VDC | ||
| Contact resistance (see note 2) |
100 mΩ max. |
|---|---|
| Operate time | 10 ms max. (approx. 3 ms) |
| Release time | 15 ms max. (approx. 4 ms) |
| Insulation resistance | 1,000 MΩ min. (at 500 VDC) |
| Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between coil and contacts 2,000 VAC, 50/60 Hz for 1 min between contacts of different polarity 1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity 250 VAC, 50/60 Hz for 1 min between coils of different polarity |
| Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) |
| Shock resistance | Destruction: 1,000 m/s2 (approx. 100G) Malfunction: 100 m/s2 (approx. 10G) |
| Endurance | Mechanical: 50,000,000 operations min. (at 18,000 operations/hr) Electrical: 100,000 operations min. (at 1,800 operations/hr, rated load) 500,000 operations min. for long-life at 2 A 100,000 operations min for long-life at 5 A |
| Ambient temperature | Operating: -25°C to 55°C (with no icing or condensation) Storage: -25°C to 55°C (with no icing or condensation) |
| Ambient humidity | Operating: 35% to 85% |
| Weight | Approx. 75 g |