Enviro-LOGO

PSC1-C-100

  • Modularly expandable to up to 272 safe inputs / outputs
  • Safe spindle monitoring To EN 61800-5-2 (Safe Drive Monitoring) for up to 12 spindles
  • 4 safe 2 A pp-switching semiconductor outputs, switchable to 2 safe p- / n-switching semiconductor outputs
  • 14 safe inputs on the base module
  • 20 switchable, safe inputs / outputs
  • 6 Signalling outputs
  • 2 safety relay contacts

Ordering data

Product type description

PSC1-C-100

Article number (order number)

103012218

EAN (European Article Number)

4030661482262

eCl@ss number, version 12.0

27-24-22-07

eCl@ss number, version 11.0

27-24-22-07

eCl@ss number, version 9.0

27-24-22-07

ETIM number, version 7.0

EC000236

ETIM number, version 6.0

EC000236

Approvals – Standards

Certificates

TÜV

cULus

EAC

General data

Terminal (mechanical)

Removable screw terminals

Gross weight

858 g

General data – Features

Number of pulse outputs (test pulse output)

6

Number of relay outputs (1-channel)

2

Number of digital fail-safe inputs

14

Number of digital fail-safe in-/outputs

20

Number of fail-safe digital outputs

4

Number of signalling outputs

6

Anzahl der Erweiterungsbaugruppen, maximal

8

Safety classification
Performance Level, up to

e

Category

4

PFH value

1.22 x 10⁻⁸ /h

Safety Integrity Level (SIL), suitable for applications in

3

Mission time

20 Year(s)

Mechanical data

Mounting

can be clipped into standard rail

Mechanical data – Connection technique

Cable section, minimum

0.2 mm²

Cable section, maximum

2.5 mm²

Wire cross-section, minimum

24 AWG

Wire cross-section, maximum

12 AWG

Mechanical data – Dimensions

Width

90 mm

Height

100 mm

Depth

115 mm

Ambient conditions

Degree of protection

IP20

Ambient temperature, minimum

+0 °C

Ambient temperature, maximum

+50 °C

Storage and transport temperature, minimum

-25 °C

Storage and transport temperature, maximum

+70 °C

Relative humidity, minimum

5 %

Relative humidity, maximum

85 %

Note (Relative humidity)

non-condensing

Permissible installation altitude above sea level, maximum

2,000 m

Ambient conditions – Insulation values

Overvoltage category

III

Degree of pollution

2

Electrical data

Operating voltage, minimum

20.4 VDC

Operating voltage, maximum

28.8 VDC

Electrical data – Safety digital outputs

Rated operating current (safety outputs)

2,000 mA

Design of control elements

short-circuit proof, p-type (Q2 und Q3)

Electrical data – Safe relay outputs

Voltage, Utilisation category AC-15

230 VAC

Current, Utilisation category AC-15

2 A

Voltage, Utilisation category DC-13

24 VDC

Current, Utilisation category DC-13

2 A