Product type description |
PSC1-C-10 |
Article number (order number) |
103012194 |
EAN (European Article Number) |
4030661482101 |
eCl@ss number, version 12.0 |
27-24-22-07 |
eCl@ss number, version 11.0 |
27-24-22-07 |
eCl@ss number, version 9.0 |
27-24-22-07 |
ETIM number, version 7.0 |
EC000236 |
ETIM number, version 6.0 |
EC000236 |
Certificates |
TÜV cULus EAC |
Terminal (mechanical) |
Removable screw terminals |
Gross weight |
500 g |
Number of pulse outputs (test pulse output) |
2 |
Number of relay outputs (1-channel) |
2 |
Number of digital fail-safe inputs |
14 |
Number of fail-safe digital outputs |
4 |
Number of signalling outputs |
2 |
Anzahl der Erweiterungsbaugruppen, maximal |
2 |
Safety classification |
Performance Level, up to |
e |
Category |
4 |
PFH value |
1.26 x 10⁻⁸ /h |
Safety Integrity Level (SIL), suitable for applications in |
3 |
Mission time |
20 Year(s) |
Mounting |
can be clipped into standard rail |
Cable section, minimum |
0.2 mm² |
Cable section, maximum |
2.5 mm² |
Wire cross-section, minimum |
24 AWG |
Wire cross-section, maximum |
12 AWG |
Width |
45 mm |
Height |
100 mm |
Depth |
115 mm |
Degree of protection |
IP20 |
Ambient temperature, minimum |
+0 °C |
Ambient temperature, maximum |
+50 °C |
Storage and transport temperature, minimum |
-25 °C |
Storage and transport temperature, maximum |
+70 °C |
Relative humidity, minimum |
5 % |
Relative humidity, maximum |
85 % |
Note (Relative humidity) |
non-condensing |
Permissible installation altitude above sea level, maximum |
2,000 m |
Overvoltage category |
III |
Degree of pollution |
2 |
Operating voltage, minimum |
20.4 VDC |
Operating voltage, maximum |
28.8 VDC |
Rated operating current (safety outputs) |
2,000 mA |
Design of control elements |
short-circuit proof, p-type (Q2 und Q3) |
Voltage, Utilisation category AC-15 |
230 VAC |
Current, Utilisation category AC-15 |
2 A |
Voltage, Utilisation category DC-13 |
24 VDC |
Current, Utilisation category DC-13 |
2 A |
Electromagnetic compatibility |
DIN EN 62061 DIN EN 61800-3 |
Interfering radiation |
DIN EN 61000-6-4 |
EMC rating |
DIN EN 61000-6-7 DIN EN 61326-3 DIN EN 61000-6-2 |
Scope of delivery |
Backplane bus connector Connector terminals |