• Wiring work can be shortened by as much as 60%* compared to conventional screw terminal sockets by combining with push-in plus terminal sockets (PYF-[]-PU) that feature light insertion force and strong pull-out strength to achieve less wiring work.
• The standard models include models that are compliant with the UL, CSA, and SEV safety standards and with the Electrical Appliances and Material Safety Act.
• Equipped with an arc barrier for arc interruption.
• Withstand voltages up to 2,000 V.
• New built-in diode and built-in CR circuit models have joined the series.
• The lineup also includes models that are compliant with the LR and VDE safety standards.
* When both push-in plus terminals and screw terminal sockets are combined with plug-in terminal types (according to actual OMRON measurements as of November 2015)
Item | Rated current (mA) |
Coil resist- ance (Ω) |
Coil inductance (H) | Must- operate voltage (V) |
Must- release voltage (V) |
Maximum voltage (V) |
Power con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60Hz | Armature OFF |
Armature ON |
||||||
AC | 12 | 106.5 | 91 | 46 | 0.17 | 0.33 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 1.0 to 1.2 (at 60 Hz) |
24 | 53.8 | 46 | 180 | 0.69 | 1.3 | |||||
50 | 25.7 | 22 | 788 | 3.22 | 5.66 | |||||
100/110 | 11.7/12.9 | 10/11 | 3,750 | 14.54 | 24.6 | Approx. 0.9 to 1.1 (at 60 Hz) |
||||
110/120 | 9.9/10.8 | 8.4/9.2 | 4,430 | 19.2 | 32.1 | |||||
200/220 | 6.2/6.8 | 5.3/5.8 | 12,950 | 54.75 | 94.07 | |||||
220/240 | 4.8/5.3 | 4.2/4.6 | 18,790 | 83.5 | 136.4 | |||||
DC | 6 | 150 | 40 | 0.16 | 0.33 | 10% min. *2 |
Approx. 0.9 | |||
12 | 75 | 160 | 0.73 | 1.37 | ||||||
24 | 36.9 | 650 | 3.2 | 5.72 | ||||||
48 | 18.5 | 2,600 | 10.6 | 21.0 | ||||||
100/110 | 9.1/10 | 11,000 | 45.6 | 86.2 |
Item | Rated current (mA) |
Coil resist- ance (Ω) |
Coil inductance (H) | Must- operate voltage (V) |
Must- release voltage (V) |
Maximum voltage (V) |
Power con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60Hz | Armature OFF |
Armature ON |
||||||
AC | 12 | 159 | 134 | 24 | 0.12 | 0.21 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 1.6 to 2.0 (at 60 Hz) |
24 | 80 | 67 | 100 | 0.44 | 0.79 | |||||
100/110 | 14.1/16 | 12.4/13.7 | 2,300 | 10.5 | 18.5 | |||||
200/220 | 9.0/10.0 | 7.7/8.5 | 8,650 | 34.8 | 59.5 | |||||
DC | 12 | 112 | 107 | 0.45 | 0.98 | 10% min. *2 |
Approx. 1.4 | |||
24 | 58.6 | 410 | 1.89 | 3.87 | ||||||
48 | 28.2 | 1,700 | 8.53 | 13.9 | ||||||
100/110 | 12.7/13 | 8,500 | 29.6 | 54.3 |
Item | Rated current (mA) |
Coil resist- ance (Ω) |
Coil inductance (H) | Must- operate voltage (V) |
Must- release voltage (V) |
Maximum voltage (V) |
Power con- sumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage (V) |
50 Hz | 60Hz | Armature OFF |
Armature ON |
||||||
AC | 12 | 199 | 170 | 20 | 0.1 | 0.17 | 80% max. *1 |
30% min. *2 |
110% of rated voltage |
Approx. 1.95 to 2.5 (at 60 Hz) |
24 | 93.6 | 80 | 78 | 0.38 | 0.67 | |||||
100/110 | 22.5/25.5 | 19/21.8 | 1,800 | 10.5 | 17.3 | |||||
200/220 | 11.5/13.1 | 9.8/11.2 | 6,700 | 33.1 | 57.9 | |||||
DC | 12 | 120 | 100 | 0.39 | 0.84 | 10% min. *2 |
Approx. 1.5 | |||
24 | 69 | 350 | 1.41 | 2.91 | ||||||
48 | 30 | 1,600 | 6.39 | 13.6 | ||||||
100/110 | 15/15.9 | 6,900 | 32.0 | 63.7 |
Classification | 1 pole | Double-, 3-, and 4-pole models |
Bifurcated contacts | |||||
---|---|---|---|---|---|---|---|---|
Load | Resistive load |
Inductive load (cos φ = 0.4, L/R = 7 ms) |
Resistive load |
Inductive load (cos φ = 0.4, L/R = 7 ms) |
Resistive load |
Inductive load (cos φ = 0.4, L/R = 7 ms) |
||
Contact type | Single | Bifurcated | ||||||
Contact materials |
Ag alloy | Ag | ||||||
Rated load | 15 A at 110 VAC 15 A at 24 VDC |
10 A at 250 VAC | 10 A at 110 VAC 7 A at 24 VDC |
10 A at 110 VAC 10 A at 24 VDC |
10 A at 250 VAC | 7.5 A at 110 VAC 5 A at 24 VDC 5 A at 24 VDC |
5 A at 110 VAC 5 A at 24 VDC |
4 A at 110 VAC 4 A at 24 VDC |
Electrical endurance*1 | 200,000 operations min. |
200,000 operations min. |
200,000 operations min. |
3-, 4-pole: 200,000 operations min. 2-pole: 500,000 operations min. |
50,000 operations min. |
3-, 4-pole: 200,000 operations min. 2-pole: 500,000 operations min. |
2-pole: 500,000 operations min. | |
Rated carry current |
15 A | 10 A | 7 A | |||||
Maximum contact voltage |
250 VAC 125 VDC |
250 VAC 125 VDC |
250 VAC 125 VDC |
|||||
Maximum contact current |
15 A | 10 A | 7 A |
Type | Single-pole and double-pole models (standard models and bifurcated contact models) |
Single-pole, double-pole models (models with built-in operation indicators, models with built-in diodes, and models with built-in CR circuits), 3-pole and 4-pole models |
---|---|---|
Ambient operating temperature |
-25 to 55°C (with no icing or condensation) *2 |
-25 to +40°C (with no icing or condensation) *3 |
Ambient operating humidity |
5% to 85% |
Type | Standard models, models with built-in operation indicators, models with built-in CR circuits, and models with built-in diodes |
Bifurcated contacts | |
---|---|---|---|
Contact resistance *1 | 50 mΩ max. | ||
Operating time *2 | 25 ms max. | ||
Release time *2 | 25 ms max. | ||
Maximum operating frequency |
Mechanical | 18,000 operations/h | |
Rated load | 1,800 operations/h | ||
Insulation resistance *3 | 100 MΩ min. | ||
Dielectric strength |
Between coil and contacts |
2,000 VAC at 50/60 Hz for 1 min. | |
Between contacts of different polarity |
|||
Between contacts of the same polarity |
1,000 VAC at 50/60 Hz for 1 min. | ||
Vibration resistance |
Destruction | 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) | |
Malfunction | 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) | ||
Shock resistance |
Destruction | 1,000 m/s2 | |
Malfunction | 200 m/s2 | ||
Endurance | Mechanical | AC: 50,000,000 operations min. DC: 100,000,000 operations min. (switching frequency: 18,000 operations/h) |
|
Failure rate P value (reference value) *4 |
100 mA at 5 VDC | 10mA at 5 VDC | |
Weight | 1-pole and 2-pole: 40 g, 3-pole: Approx. 50 g, 4-pole: Approx. 70 g |
Item | LY1, 100 VAC | LY2, 100 VAC | ||||
---|---|---|---|---|---|---|
Load type | Conditions | Operating frequency |
Electrical life (×10,000 operations min.) |
Conditions | Operating frequency |
Electrical life (×10,000 operations min.) |
AC motor | 400 W, 100 VAC single-phase with 35-A inrush current, 7-A current flow |
ON for 10 s, OFF for 50 s |
5 | 200 W, 100 VAC single-phase with 25-A inrush current, 5-A current flow |
ON for 10 s, OFF for 50 s |
20 |
AC lamp | 300 W, 100 VAC with 51-A inrush current, 3-A current flow |
ON for 5 s, OFF for 55 s |
10 | 300 W, 100 VAC with 51-A inrush current, 3-A current flow |
ON for 5 s, OFF for 55 s |
8 |
500 W, 100 VAC with 78-A inrush current, 5-A current flow |
2.5 | |||||
Capacitor (2,000 μF) |
24 VDC with 50-A inrush current, 1-A current flow |
ON for 1 s, OFF for 6 s |
10 | 24 VDC with 50-A inrush current, 1-A current flow |
ON for 1 s, OFF for 15 s |
1 |
24 VDC with 20-A inrush current, 1-A current flow |
15 | |||||
AC solenoid | 50 VA with 2.5-A inrush current, 0.25-A current flow |
ON for 1 s, OFF for 2 s |
150 | 50 VA with 2.5-A inrush current, 0.25-A current flow |
ON for 1 s, OFF for 2 s |
100 |
100 VA with 5-A inrush current, 0.5-A current flow |
80 | 100 VA with 5-A inrush current, 0.5-A current flow |
50 |
Item | LY4, 100 VAC | ||
---|---|---|---|
Load type | Conditions | Operating frequency | Electrical life (×10,000 operations min.) |
AC motor | 200 W, 200 VAC three-phase with 5-A inrush current, 1-A current flow |
ON for 10 s, OFF for 50 s |
50 |
750 W, 200 VAC three-phase with 18-A inrush current, 3.5-A current flow |
7 | ||
AC lamp | 300 W, 100 VAC with 51-A inrush current, 3-A current flow |
ON for 5 s, OFF for 55 s |
5 |
Capacitor (2,000 μF) |
24 VDC with 50-A inrush current, 1-A current flow |
ON for 1 s, OFF for 15 s |
0.5 |
24 VDC with 20-A inrush current, 1-A current flow |
ON for 1 s, OFF for 2 s |
20 | |
AC solenoid | 50 VA with 2.5-A inrush current, 0.25-A current flow |
ON for 1 s, OFF for 2 s |
100 |
100 VA with 5-A inrush current, 0.5-A current flow |
50 |
Model | Continuous carry current |
Dielectric strength | Insulation resistance *1 |
Remarks |
---|---|---|---|---|
PTF-[]-PU(L) | 10 A | Between contact terminals of same polarity: 2,000 VAC, 1 min |
1,000 MΩ min. |
|
Between contact terminals of different polarity: 2,000 VAC, 1 min |
||||
Between coil and contact terminals: 2,000 VAC, 1 min | ||||
PTFZ-[][]-E | 12 A (@70°C) 15 A (@50°C) *2 |
Between contact terminals of different polarity: 2,500 VAC, 1 min |
1,000 MΩ min. |
|
Between contact terminals of same polarity: 2,500 VAC, 1 min |
||||
Between ground terminals: 2,500 VAC, 1 min | ||||
Between coil and contact terminals: 2,500 VAC, 1 min | ||||
PTF[][]A(-E) | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT-[][] | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT[][]-0 | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. | |
PT[][]QN | 10 A | Between terminals: 2,000 VAC for 1 min | 100 MΩ min. |