• The soft-start function allows a smooth startup of motors by holding down the starting current, and functions like an inverter.
• Comply with UL, CSA, CCC, IEC, and JEM requirements.
• Mount with screws or to DIN tracks.
• Compact monoblock construction (W: 80 × H: 100 × D: 100 mm) with a heat sink.
• Snubber circuit and varistor are built-in.
• Operation indicator.
Rated supply voltage | 12 to 24 VDC |
---|---|
Operating voltage range | 10.2 to 26.4 VDC |
Current consumption | 100 mA max. (at 12 to 24 VDC) |
Input current | 10 mA max. (at 12 to 24 VDC) |
---|---|
Input method No-voltage input (short-circuiting and opening inputs) (See note.) |
Short-circuiting or opening terminals 1 and COM or 2 (+) and 1 SSR input turned ON: A maximum residual voltage of 2 V between short-circuited terminals SSR input turned OFF: A maximum leakage current of 0.15 mA Relay input: For minute signals |
Note: Refer to Safety Precautions for the G3J-T, G3J-S, and G3J.
Item | G3J-S405BL | G3J-S403BL | G3J-S211BL | G3J-S205BL | |
---|---|---|---|---|---|
Rated load voltage | 200 to 400 VAC (50/60 Hz) | 200 to 240 VAC (50/60 Hz) | |||
Load voltage range | 180 to 440 VAC (50/60 Hz) | 180 to 264 VAC (50/60 Hz) | |||
Rated carry current | 5.5 A (Ta = 40°C) | 2.4 A (Ta = 40°C) | 11.1 A (Ta = 40°C) | 4.8 A (Ta = 40°C) | |
Min. load current | 0.5 A | ||||
Peak-value current resistivity |
220 A, 60 Hz, 1 cycle | 96 A, 60 Hz, 1 cycle | 350 A, 60 Hz, 1 cycle | 150 A, 60 Hz, 1 cycle | |
Overload resistance | Refer to Iengneering data on Datasheet. | ||||
Closed current (effective value) |
AC3 | 55 A | 24 A | 111 A | 48 A |
AC4 | 66 A | 28.8 A | 133.2 A | 57.6 A | |
Breaking current (effective value) |
AC3 | 44 A | 19.2 A | 88.8 A | 38.4 A |
AC4 | 55 A | 24 A | 111 A | 48 A | |
Applicable load | 3-phase inductive motor (AC3 AC4 AC53-a) |
380 to 400 VAC, 2.2 kW, 5.5 A |
380 to 400 VAC, 0.75 kW, 2.4 A |
200 to 220 VAC, 2.2 kW, 11.1 A |
200 to 220 VAC, 0.75 kW, 4.8 A |
Motors passing the AC3-class, AC4-class, and AC53-a-class switching frequency test (Ta = 40°C) under conditions specified by OMRON. | |||||
Resistive load (AC1) (See note.) |
200 to 400 VAC, 5.5 A |
200 to 400 VAC, 2.4 A |
200 to 240 VAC, 11.1 A |
200 to 240 VAC, 4.8 A |
Note: No single-phase load can be connected.
Item | G3J-S405BL | G3J-S403BL | G3J-S211BL | G3J-S205BL |
---|---|---|---|---|
Ramp-up time | Set within a range from 1 to 25 s. | |||
Reset time | 5/6 cycles of load power supply + 1 ms max. | |||
Starting torque | Set within a range from 200% to 450% In. | |||
Output ON-voltage drop |
1.8 VRMS max. | 1.6 VRMS max. | ||
Leakage current | 20 mA max. (at 400 VAC) | 10 mA max. (at 200 VAC) | ||
Insulation resistance | 100 MΩ min. (at 500 VDC) | |||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||
Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude | |||
Shock resistance | Destruction: 294 m/s2 | |||
Ambient temperature | Operating: -20°C to 60°C (with no icing or condensation) Storage: -30°C to 70°C (with no icing or condensation) |
|||
Ambient humidity | Operating: 45% to 85% | |||
Weight | 730 g max. | |||
Certified standards | UL (File No.E64562), CSA (File No.LR35535), KEMA (File No.71-105822, EN60947-4-2) CCC GB/T 14048.6 No. 2016010304855598 (G3J-S405BL, G3J-S403BL) CCC GB/T 14048.6 No. 2016010304855599 (G3J-S211BL, G3J-S205BL) IEC947-4-1 File No. 96.2597.02 |
|||
EMC | Emission AC mains IEC947-4-2, CISPR 11 Class A Emission Electromagnetic IEC947-4-2, CISPR 11 Class A Immunity ESD IEC947-4-2, IEC801-2: 4 kV contact discharge, 8 kV air discharge Immunity Electromagnetic IEC947-4-2, IEC1000-4-3 10 V/m (80 MHz to 1 GHz) Immunity EFT IEC947-4-2, IEC801-4: 2 kV AC power-signal line Immunity Surge transient IEC947-4-2, IEC1000-4-5 1 kV differential mode, 2 kV common mode Immunity RF disturbance IEC947-4-2, IEC/DIS1000-4-6 10 V (0.15 to 80 MHz) |