• Use cycle control to achieve power control with little noise.
• Used in combination with the G3PA to connect to single- and three-phase loads.
• Three types of input method available: Internal adjuster, external adjuster, or DC signals from 4 to 20 mA.
• Streamline design. Both DIN track mounting and screw mounting possible.
• Use linking terminals for close mounting of the G3PA.
• Built-in isolation transformer.
• Power supply range: 100 to 240 V.
Rated power supply current | 50 Hz | 100 to 240 VAC | 40 mA max. |
---|---|---|---|
60 Hz | 100 to 240 VAC | ||
Output signal | 20 mA max. at 12 VDC ±15% (at 25°C) | ||
Input signal | Current signal: 4 to 20 mA (input impedance: 352 Ω) Internal adjuster: 50 kΩ (1/4 W) External adjuster: 50 kΩ (1/4 W) |
||
Output cycle rate | 0 to 100% | ||
Control cycle | 0.2 s | ||
Number of operable Units | 3 G3PA-VD Relays max. |
Power supply voltage range | 75 to 264 VAC |
---|---|
Dielectric strength | 1,500 VAC, 50/60 Hz for 1 minute (between AC power supply and input/output terminals) |
Insulation resistance | 100 MΩ max. (at 500 VDC) |
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (when mounted to DIN track) |
Shock resistance | 300 m/s2 (approx. 30 G) |
Storage temperature | -30 to 100°C (with no icing or condensation) |
Ambient temperature | -30 to 80°C (with no icing or condensation) |
Ambient humidity | 45% to 85% |
Weight | Approx. 100 g |