• Easy setting using DIP switch.
• Models with two alarms added to Series, ideal for temperature alarm applications.
• Universal-input (thermocouple/platinum resistance thermometer) models also available.
• Clearly visible digital display with character height of 13.5 mm.
• Models available with black in addition to white cases.
• RoHS compliant.
Supply voltage | 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz; 24 VDC |
|
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 5 VA 24 VAC: 3 VA, 24 VDC: 2 W |
|
Sensor input | Thermocouple input type: K, J, L Platinum resistance thermometer input type: Pt100, JPt100 Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100 |
|
Control output |
Relay output | SPST-NO, 250 VAC, 3A (resistive load) |
Voltage output (for driving the SSR) |
12 VDC, 21 mA (with short-circuit protection circuit) | |
Control method | ON/OFF or 2-PID (with auto-tuning) | |
Alarm output | SPST-NO, 250 VAC, 1A (resistive load) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display (character height: 13.5 mm) and deviation indicators | |
Other functions | Setting change prohibit (key protection) Input shift Temperature unit change (°C/°F) Direct/reverse operation Temperature range, Sensor switching (K/J/L, Pt100/JPt100) Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models. Control period switching 8-mode alarm output Sensor error detection |
|
Ambient operating temperature |
-10 to 55°C (with no condensation or icing); with 3-year guarantee: -10 to 50°C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) |
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
2. Models for 24 VAC/DC can also be manufactured.
Setting accuracy | Thermocouple (See note 1.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. |
|
---|---|---|
Indication accuracy (ambient temperature of 23°C) |
||
Influence of temperature | R thermocouple inputs: (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. |
|
Influence of voltage | ||
Influence of EMS. (at EN61326-1) |
||
Hysteresis (for ON/OFF control) |
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models) | |
Proportional band (P) | 1 to 999°C (automatic adjustment using auto-tuning/self-tuning) | |
Integral time (I) | 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning | |
Derivative time (D) | 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning) | |
Alarm output range | Absolute-value alarm: Same as the control range Other: 0 to input setting range full scale (°C or °F) Alarm hysteresis: 0.2°C or °F (fixed) |
|
Control period | 2/20 s | |
Sampling period | 500 ms | |
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity | |
Vibration resistance |
Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions | |
Shock resistance |
Malfunction | 100 m/s2 min., 3 times each in 6 directions |
Destruction | 300 m/s2 min., 3 times each in 6 directions | |
Life expectancy |
Electrical | 100,000 operations min. (relay output models) |
Weight | Approx. 120 g (Controller only) | |
Degree of protection | Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00 | |
Memory protection | EEPROM (non-volatile memory) (number of writes: 1,000,000) | |
EMC | EMI Radiated: EN 55011 Group 1 Class A EMI Conducted: EN 55011 Group 1 Class A ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2), 8 kV air discharge (level 3) Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3), 10 V/m (900 MHz pulse modulated) Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2) Noise Immunity (First Transient Burst Noise): EN 61000-4-4 Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3) Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV, Output line (relay output): Normal mode 1 kV; Common mode 2 kV Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage) |
|
Approved standards | UL 61010-1 (listing) CSA C22.2 No.1010-1 |
|
Conformed standards | EN61326-1 (See note 3.), EN61010-1, IEC61010-1 VDE 0106 Part 100 (finger protection), when the terminal cover is mounted. |