Accuracy of
operating time |
±0.01% ±0.05 s max. *1 |
Setting error |
Influence of voltage |
Influence of
temperature |
Influence of EMS.
(at EN61326-1) |
Time accuracy |
±15 s per month (at 25°C) |
Memory protection |
Continuous use: 5 years min. (at 25°C); Power-interruption rate of 50%: 10 years min. (at
25°C) *2 (lithium battery) |
Insulation resistance |
100 MΩ min. (between current-carrying terminals and exposed non-current-carrying metal
parts, between operating power supply circuit and control output circuit and between non-
continuous contacts) |
Dielectric strength |
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-
current-carrying metal parts and between operating power supply circuit and control output
circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Noise immunity |
1.5 kV (between power terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
Vibration resistance |
Destruction:10 to 55 Hz with 0.375-mm single amplitude, four cycles each in three directions
(8 minutes per cycle)
Malfunction:10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions |
Shock resistance |
Destruction:300 m/s2 3 times each in 6 directions
Malfunction:100 m/s2 3 times each in 6 directions |
Ambient temperature |
Operating: -10°C to 55°C (with no icing)
Storage: -25°C to 65°C (with no icing) |
Ambient humidity |
Operating: 35% to 85% |
Life expectancy |
Mechanical (at 20°C):
100,000 operations min.
Electrical (at 20°C):
50,000 operations min. (15 A, 250 VAC, resistive load)
50,000 operations min. (1 HP, 250 VAC, motor load)
50,000 operations min. (10 A, 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (100 W, 100 VAC, lamp load)
10,000 operations min. (300 W, 100 VAC, lamp load) |
Approved safety
standards |
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage
category II)
Conforms to VDE0106/P100 (finger protection).
Conforms to Electrical Appliance and Material Safety Law (for Japan) |
EMC |
(EMI) EN61326-1 *3
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61326-1 *3
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2); 8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz,
1.4 to 2 GHz) (level 3)
Immunity Conducted
Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (according to EN61000-6-2)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3); 1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 2); 2 kV line to
ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Immunity Magnetic Power Field: EN61000-4-8: 30 A/m |
Case color |
Light gray (Munsell 5Y7/1) |
Weight |
H5F-B: approx. 115 g; H5F-KB: approx. 160 g; H5F-FB: approx. 130 g |