The new models carry on the simple operation and low cost of the series.
A wide variety of applications can be handled by using program settings with up to 256 segments.
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC |
|
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 12 VA 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) |
|
Sensor input | Any of the following can be selected. Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V |
|
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N.) |
|
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output |
Relay output | Output Unit (Install the Output Unit (sold separately).) |
Voltage output (for driving SSR) |
||
Current output | ||
Linear voltage output | ||
Auxiliary output |
Number of outputs | 2 or 3 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
|
Event input |
Number of outputs | 2 or 4 (with an E53-AKB) |
External contact input specifications |
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. |
||
Current flow: Approx. 7 mA per contact | ||
Logic operations |
Number of operations | 8 max. |
Operations | Logic operation: Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.) Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min Output inversion: Possible |
|
Output | One work bit per operation | |
Work bit assignment |
Any of The following can be assigned to up to eight work bits (logic operation results): operation commands (assigned to event inputs)* , auxiliary outputs, or control outputs. * Application is possible with models that do not have event inputs by using an internal assignment. |
|
Transfer outputs |
Number of outputs | 1 max. (Depends on model. Models with transfer output (F in model number) |
Output specifications | Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 |
|
RSP input |
Number of inputs | 1 |
Signal type | Current input: 4 to 20 mA (input impedance: 150 Ω ± 10%) | |
Analog input scaling | Scaling of signal to engineering units (EU) – 19,999 to 30,000 (display: 30,000 max.) |
|
Accuracy | ( ± 0.2% of FS) ± 1 digit max. | |
Input sampling period | 60 ms | |
Setting method | Set digitally using keys on the front panel or by using the RSP input. | |
Indication method | 11-segment digital display and individual indicators (7-segments displays also possible) Character height: E5AN-HT: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-HT: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm Three displays: PV/SV/Program number/Segment number, PV/SV/MV, or PV/ SV/Remaining segment time. Number of digits: 5 for PV and SV, 4 for MV |
|
Other functions | Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout detection (including SSR failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input digital filter, temperature input shift, run/reset, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, automatic cooling coefficient adjustment, program control functions, etc. |
|
Ambient operating temperature | -10 to 55 °C (with no condensation or icing), for 3-year warranty: -10 to 50 °C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65 °C (with no condensation or icing) |
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Set value |
Alarm type | Alarm output operation | Description of function | |
---|---|---|---|---|
When alarm value X is positive |
When alarm value X is negative |
|||
0 | Alarm function OFF | Output OFF | No alarm | |
1 | Upper- and lower- limit *1 |
*2 | Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). |
|
2 | Upper-limit | Set the upward deviation in the set point by setting the alarm value (X). |
||
3 | Lower-limit | Set the downward deviation in the set point by setting the alarm value (X). |
||
4 | Upper- and lower- limit range *1 |
*3 | Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). |
|
5 | Upper- and lower- limit with standby sequence *1 |
*5 |
*4 | A standby sequence is added to the upper- and lower- limit alarm (1). *7 |
6 | Upper-limit with standby sequence |
A standby sequence is added to the upper-limit alarm (2). *7 |
||
7 | Lower-limit with standby sequence |
A standby sequence is added to the lower-limit alarm (3). *7 |
||
8 | Absolute-value upper-limit |
The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. |
||
9 | Absolute-value lower-limit |
The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. |
||
10 | Absolute-value upper-limit with standby sequence |
A standby sequence is added to the absolute-value upper-limit alarm (8). *7 |
||
11 | Absolute-value lower-limit with standby sequence |
A standby sequence is added to the absolute-value lower-limit alarm (9). *7 |
||
12 | LBA (alarm 1 type only) |
— | *7 | |
13 | PV change rate alarm |
— | *7 | |
14 | RSP absolute value upper limit *6 |
The alarm turns ON when the remote SP (RSP) is larger than the alarm value (X). This alarm functions in both Local SP and Remote SP Modes. |
||
15 | RSP absolute value lower limit *6 |
The alarm turns ON when the remote SP (RSP) is smaller than the alarm value (X). This alarm functions in both Local SP and Remote SP Modes. |
Indication accuracy | Thermocouple: (± 0.1% of indicated value or ± 1 °C, whichever is greater) ± 1 digit max. *1 Platinum resistance thermometer: (± 0.1% of indicated value or ± 0.5 °C, whichever is greater) ± 1 digit max. Analog input: ± 0.1% FS ± 1 digit max. CT input: ± 5% FS ± 1 digit max. |
|
---|---|---|
Transfer output accuracy | ± 0.3% FS max. | |
Influence of temperature *2 |
Thermocouple input (R, S, B, W, PL II): (± 1% of PV or ± 10 °C, whichever is greater) ±1 digit max. Other thermocouple input: (± 1% of PV or ± 4 °C, whichever is greater) ± 1 digit max. *3 Platinum resistance thermometer: (± 1% of PV or ± 2 °C, whichever is greater) ± 1 digit max. Analog input: (± 1%FS) ± 1 digit max. |
|
Influence of voltage *2 | ||
Influence of EMS. (at EN 61326-1) |
||
Input sampling period | 60 ms | |
Hysteresis | Temperature input: 0.1 to 3240.0 °C or °F (in units of 0.1 °C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) |
|
Proportional band (P) | Temperature input: 0.1 to 3240.0 °C or °F (in units of 0.1 °C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) |
|
Integral time (I) | 0.0 to 3240.0 s (in units of 0.1 s) | |
Derivative time (D) | 0.0 to 3240.0 s (in units of 0.1 s) | |
Control period | 0.5, 1 to 99 s (in units of 1 s) | |
Manual reset value | 0.0 to 100.0% (in units of 0.1%) | |
Alarm setting range | -19999 to 32400 (decimal point position depends on input type) | |
Affect of signal source resistance |
Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) |
|
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) | |
Vibration resistance |
Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions | |
Shock resistance |
Malfunction | 100 m/s2, 3 times each in X, Y, and Z directions |
Destruction | 300 m/s2, 3 times each in X, Y, and Z directions | |
Weight | E5AN-HT | Controller: Approx. 310 g, Mounting Bracket: Approx. 100 g |
E5EN-HT | Controller: Approx. 260 g, Mounting Bracket: Approx. 100 g | |
Degree of protection | Front panel: IP66, Rear case: IP20, Terminals: IP00 | |
Memory protection | Non-volatile memory (number of writes: 1,000,000 times) | |
Setup Tool | CX-Thermo version 4.0 or higher | |
Setup Tool port | Provided on the bottom of the E5AN-HT and E5EN-HT. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5AN-HT and E5EN-HT. |
|
Standards | Approved standards |
UL 61010-1, CSA C22.2 No. 1010-1 |
Conformed standards |
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II | |
EMC | EMI: EN 61326-1 *4 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326-1 *4 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 |
Number of programs (patterns) | 8 | |
---|---|---|
Number of segments (steps) | 32 | |
Segment setting method | Time setting (Segment set with set point and time.) | |
Gradient setting (Segment type with set point, gradient, and time.) | ||
Segment times | 0 h 0 min to 99 h 59 min | |
0 min 0 s to 99 min 59 s | ||
Alarm setting | Set separately for each program. | |
Reset operation | Select either stopping control or fixed SP operation. | |
Startup operation | Select continuing, resetting, manual operation, or run mode. | |
PID sets | Number of sets | 8 |
Setting method | Set separately for each program (automatic PID group selection also supported). |
|
Alarm SP function | Select from ramp SP and target SP. | |
Program status control | Segment operation | Advance, hold |
Program operation | Program repetitions and program links | |
Wait operation | Wait method | Waiting at segment ends |
Wait width setting | Same wait width setting for all programs | |
Time signals | Number of outputs | 2 |
Number of ON/OFF Operations |
1 each per output | |
Setting method | Set separately for each program. | |
Program status output | Program end output (pulse width can be set), run output, stage output | |
Program startup operation | PV start | Select from segment 1 set point, slope-priority PV start |
Standby | 0 h 0 min to 99 h 59 min | |
0 day 0 h to 99 day 23h | ||
Operation end operation | Select from resetting, continuing control at final set point, and fixed SP control. | |
Program SP shift | Same program SP shift for all programs |
Applicable OS | Windows XP/Vista/7/8 |
---|---|
Applicable software | CX-Thermo version 4 or higher |
Applicable models | E5AN/E5EN/E5CN/E5CN-U/E5AN-H/E5EN-H/E5CN-H/E5AN-HT/E5EN-HT/ E5CN-HT |
USB interface standard | Conforms to USB Specification 1.1. |
DTE speed | 38400 bps |
Connector specifications | Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) |
Power supply | Bus power (Supplied from USB host controller.) |
Power supply voltage | 5 VDC |
Current consumption | 70 mA |
Ambient operating temperature | 0 to 55°C (with no condensation or icing) |
Ambient operating humidity | 10% to 80% |
Storage temperature | – 20 to 60°C (with no condensation or icing) |
Storage humidity | 10% to 80% |
Altitude | 2,000 m max. |
Weight | Approx. 100 g |
Transmission line connection method | RS-485, RS-422: Multipoint RS-232C: Point-to-point |
---|---|
Communications | RS-485 (two-wire, half duplex) RS-422 (four-wire, half duplex) or RS-232C |
Synchronization method | Start-stop synchronization |
Protocol | CompoWay/F or Modbus |
Baud rate | 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps |
Transmission code | ASCII (CompoWay/F) |
RTU (Modbus) | |
Data bit length * | 7 or 8 bits |
Stop bit length * | 1 or 2 bits |
Error detection | Vertical parity (none, even, odd) Block check character (BCC) with CompoWay/F or CRC-16 Modbus |
Flow control | None |
Interface | RS-485, RS-422, or RS-232C |
Retry function | None |
Communications buffer | 217 bytes |
Communications response wait time | 0 to 99 ms Default: 20 ms |
Dielectric strength | 1,000 VAC for 1 min |
---|---|
Vibration resistance | 50 Hz, 98 m/s2 |
Weight | E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g |
Accessories (E54-CT3 only) | Armatures (2) Plugs (2) |
CT input (for heater current detection) |
Models with detection for single-phase heaters: One input Models with detection for single-phase or three-phase heaters: Two inputs |
---|---|
Maximum heater current | 50 A AC |
Input current indication accuracy | ±5% FS ±1 digit max. |
Heater burnout alarm setting range *1 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |
SSR failure alarm setting range *2 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms |
Heater overcurrent alarm setting range *3 |
0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |