• High-resolution display with 5 digits/0.01°C display in a compact Controller (48 x 48 mm).
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller.
• A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.
• Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0)
• Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter.
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC |
|
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) |
|
Sensor input | Any of the following can be selected (i.e., fully universal input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V |
|
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output |
Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) |
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 * | |
Linear voltage output | 0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000 | |
Auxiliary output |
Number of outputs | 2 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |
Event input |
Number of outputs | 2 |
External contact input specifications |
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Logic operations |
Number of operations | 8 max. (Combinations can be made using work bits.) |
Operations | • Logic operation: Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.) • Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min • Output inversion: Possible |
|
Outputs | One work bit per operation | |
Work bit assignments |
Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations, auxiliary outputs, or control outputs. | |
Transfer outputs |
Number of outputs | 1 max. |
Output specifications |
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000 | |
RSP input | Not supported | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicators (7-segments displays also possible) Character height: PV: 11 mm, SV: 6.5 mm |
|
Bank switching | Supported (number of banks: 8) Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.) |
|
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display, logic operations, automatic cooling coefficient adjustment | |
Ambient operating temperature | -10 to 55°C (with no condensation or icing), for 3-year warranty: -10 to 50°C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) |
* For models with current outputs, control output 1 can be used as a transfer output.
Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
Set value |
Alarm type | Alarm output operation | Description of function | |
---|---|---|---|---|
When alarm value X is positive |
When alarm value X is negative |
|||
0 | Alarm function OFF | Output OFF | No alarm | |
1 *1 | Upper- and lower-limit | *2 | Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). |
|
2 | Upper-limit | Set the upward deviation in the set point by setting the alarm value (X). |
||
3 | Lower-limit | Set the downward deviation in the set point by setting the alarm value (X). |
||
4 *1 | Upper- and lower-limit range | *3 | Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). |
|
5 *1 | Upper- and lower-limit with standby sequence |
*5
|
*4 | A standby sequence is added to the upper- and lower-limit alarm (1). *6 |
6 | Upper-limit with standby sequence |
A standby sequence is added to the upper-limit alarm (2). *6 | ||
7 | Lower-limit with standby sequence |
A standby sequence is added to the lower-limit alarm (3). *6 | ||
8 | Absolute-value upper-limit | The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. |
||
9 | Absolute-value lower-limit | The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. |
||
10 | Absolute-value upper-limit with standby sequence |
A standby sequence is added to the absolute-value upper-limit alarm (8). *6 |
||
11 | Absolute-value lower-limit with standby sequence |
A standby sequence is added to the absolute-value lower-limit alarm (9). *6 |
||
12 | LBA (alarm 1 type only) | — | *7 | |
13 | PV change rate alarm | — | *8 |
Indication accuracy | Thermocouple: (± 0.1% of indicated value or ± 1 °C, whichever is greater) ± 1 digit max. *1 Platinum resistance thermometer: (± 0.1% of indicated value or ± 0.5 °C, whichever is greater) ± 1 digit max. Analog input: ± 0.1% FS ± 1 digit max. CT input: ± 5% FS ± 1 digit max. |
|
---|---|---|
Transfer output accuracy | ± 0.3% FS max. | |
Influence of temperature *2 |
Thermocouple input (R, S, B, W, PLII): (± 1% of PV or ± 10 °C, whichever is greater) ± 1 digit max. Other thermocouple input: (± 1% of PV or ± 4 °C, whichever is greater) ± 1 digit max. *3 Platinum resistance thermometer: (± 1% of PV or ± 2 °C, whichever is greater) ± 1 digit max. Analog input: (± 1%FS) ± 1 digit max. |
|
Influence of voltage *2 | ||
Influence of EMS. (at EN 61326-1) |
||
Input sampling period | 60 ms | |
Hysteresis | Temperature input: 0.1 to 3240.0 °C or ° F (in units of 0.1 °C or ° F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) |
|
Proportional band (P) | Temperature input: 0.1 to 3240.0 °C or ° F (in units of 0.1 °C or ° F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) |
|
Integral time (I) | 0.0 to 3240.0 s (in units of 0.1 s) | |
Derivative time (D) | 0.0 to 3240.0 s (in units of 0.1 s) | |
Control period | 0.5, 1 to 99 s (in units of 1 s) | |
Manual reset value | 0.0 to 100.0% (in units of 0.1%) | |
Alarm setting range | -19999 to 32400 (decimal point position depends on input type) | |
Affect of signal source resistance |
Thermocouple: 0.1°C/Ω max. (100 Ω max.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) |
|
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) | |
Vibration resistance |
Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions | |
Shock resistance |
Malfunction | 100 m/s2, 3 times each in X, Y, and Z directions |
Destruction | 300 m/s2, 3 times each in X, Y, and Z directions | |
Weight | Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g | |
Degree of protection | Front panel: IP66, Rear case: IP20, Terminals: IP00 | |
Memory protection | Non-volatile memory (number of writes: 1,000,000 times) | |
Setup Tool | CX-Thermo version 4.0 or higher | |
Setup Tool port | Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H. An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. *4 |
|
Standards | Approved standards |
UL 61010-1, CSA C22.2 No. 1010-1 |
Conformed standards |
EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd’s standards *5 | |
EMC | EMI: EN 61326-1 *6 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326-1 *6 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Power Frequency Magnetic Field Immunity: EN 61000-4-8 Voltage Dip/Interrupting Immunity: EN 61000-4-11 |
*1. The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of
-100°C max., and U and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the
B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples in the
400 to 800°C range is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C
max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C, whichever is greater,
±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit
max.
*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: ±10°C max.
*4. External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the
same time.
*5. Refer to information on maritime standards in Safety Precautions for E5[]N/E5[]N-H for compliance with Lloyd’s
Standards.
*6. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Applicable OS | Windows XP/Vista/7/8/8.1/10 |
---|---|
Applicable software | CX-Thermo version 4 or higher |
Applicable models | E5AN/E5EN/E5CN/E5CN-U/E5AN-H/E5EN-H/E5CN-H |
USB interface standard | Conforms to USB Specification 1.1. |
DTE speed | 38400 bps |
Connector specifications | Computer: USB (type A plug) Temperature Controller: Setup Tool port (on bottom of Controller) |
Power supply | Bus power (Supplied from USB host controller.) |
Power supply voltage | 5 VDC |
Current consumption | 70 mA |
Ambient operating temperature | 0 to 55°C (with no condensation or icing) |
Ambient operating humidity | 10% to 80% |
Storage temperature | – 20 to 60°C (with no condensation or icing) |
Storage humidity | 10% to 80% |
Altitude | 2,000 m max. |
Weight | Approx. 100 g |
Transmission line connection method |
RS-485: Multipoint RS-232C: Point-to-point |
---|---|
Communications | RS-485 (two-wire, half duplex)/RS-232C |
Synchronization method | Start-stop synchronization |
Protocol | CompoWay/F, SYSWAY, or Modbus |
Baud rate | 1200, 2400, 4800, 9600, 19200, 38400, or 57600 bps |
Transmission code | ASCII (CompoWay/F, SYSWAY) RTU (Modbus) |
Data bit length * | 7 or 8 bits |
Stop bit length * | 1 or 2 bits |
Error detection | Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus |
Flow control | None |
Interface | RS-485, RS-232C |
Retry function | None |
Communications buffer | 217 bytes |
Communications response wait time |
0 to 99 ms Default: 20 ms |
* The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications
Setting Level.
Dielectric strength | 1,000 VAC for 1 min |
---|---|
Vibration resistance | 50 Hz, 98 m/s2 |
Weight | E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g |
Accessories (E54-CT3 only) | Armatures (2) Plugs (2) |
CT input (for heater current detection) | Models with detection for single-phase heaters: One input Models with detection for single-phase or three-phase heaters: Two inputs |
---|---|
Maximum heater current | 50 A AC |
Input current indication accuracy | ±5% FS ±1 digit max. |
Heater burnout alarm setting range *1 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |
SSR failure alarm setting range *2 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection OFF time: 100 ms |
Heater overcurrent alarm setting range *3 | 0.1 to 49.9 A (in units of 0.1 A) Minimum detection ON time: 100 ms |