• Reduces wiring work by 60% when combined with the P2RF-[]-PU Push-In Plus Socket
(according to actual OMRON measurements).
• Lockable test button models available.
• Built-in mechanical operation indicator.
• Provided with nameplate.
• AC type is equipped with a coil-disconnection self-diagnostic function (LED type).
• High switching power (1-pole: 10 A).
| Rated voltage | Rated current* | Coil resistance |
Coil inductance (H) (ref. value) |
Must operate voltage |
Must release voltage |
Max. voltage |
Power consumption (approx.) |
|||
|---|---|---|---|---|---|---|---|---|---|---|
| 50 Hz | 60 Hz | Armature OFF |
Armature ON |
% of rated voltage | ||||||
| AC | 24 V | 43.5 mA | 37.4 mA | 253 Ω | 0.81 | 1.55 | 80% max. | 30% max. | 110% | 0.9 VA at 60 Hz |
| 48 V | 21.8 mA | 18.8 mA | 1,040 Ω | 3.12 | 6.17 | |||||
| 110 V | 9.5 mA | 8.2 mA | 5,566 Ω | 13.33 | 26.83 | |||||
| 120 V | 8.6 mA | 7.5 mA | 7,286 Ω | 16.13 | 32.46 | |||||
| 230 V | 4.4 mA | 3.8 mA | 27,172 Ω | 72.68 | 143.9 | |||||
| 240 V | 4.2 mA | 3.7 mA | 27,800 Ω | 90.58 | 182.34 | |||||
| Rated voltage | Rated current* | Coil resistance |
Coil inductance (H) (ref. value) |
Must operate voltage |
Must release voltage |
Max. voltage |
Power consumption (approx.) |
||
|---|---|---|---|---|---|---|---|---|---|
| Armature OFF |
Armature ON |
% of rated voltage | |||||||
| DC | 6 V | 87.0 mA | 69 Ω | 0.25 | 0.48 | 70% max. | 15% min. | 110% | 0.53 W |
| 12 V | 43.2 mA | 278 Ω | 0.98 | 2.35 | |||||
| 24 V | 21.6 mA | 1,113 Ω | 3.6 | 8.25 | |||||
| 48 V | 11.4 mA | 4,220 Ω | 15.2 | 29.82 | |||||
Note:
1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of
+15%/-20% for the AC rated current and ±10% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum voltage is the maximum possible value of the voltage that can be applied to the relay coil.
It is not the maximum voltage that can be applied continuously.
| Number of poles | 1 pole | 2 poles | ||
|---|---|---|---|---|
| Load | Resistive load (cosΦ = 1) |
Inductive load (cosΦ = 0.4; L/R = 7 ms) |
Resistive load (cosΦ = 1) |
Inductive load (cosΦ = 0.4; L/R = 7 ms) |
| Rated load | 10 A at 250 VAC; 10 A at 30 VDC |
7.5 A at 250 VAC; 5 A at 30 VDC |
5 A at 250 VAC; 5 A at 30 VDC |
2 A at 250 VAC; 3 A at 30 VDC |
| Rated carry current | 10 A | 5 A | ||
| Max. switching voltage | 440 VAC, 125 VDC | 380 VAC, 125 VDC | ||
| Max. switching current | 10 A | 5 A | ||
| Max. switching power | 2,500 VA, 300 W | 1,875 VA, 150 W | 1,250 VA, 150 W | 500 VA, 90 W |
| Failure rate (reference value) * | 100 mA at 5 VDC | 10 mA at 5 VDC | ||
Note: P level: λ60 = 0.1 x 10-6/operation
*This value was measured at a switching frequency of 120 operations per minute.
| Item | 1 pole | 2 poles |
|---|---|---|
| Contact configration | SPDT | |
| Contact structure | Single | |
| Contact resistance | 100 mΩ max. | |
| Operate (set) time | 15 ms max. | |
| Release (reset) time | AC: 10 ms max.; DC: 5 ms max. (w/built-in diode: 20 ms max.) |
AC: 15 ms max.; DC: 10 ms max. (w/built-in diode: 20 ms max.) |
| Max. operating frequency |
Mechanical: 18,000 operations/hr Electrical: 1,800 operations/hr (under rated load) |
|
| Insulation resistance | 1,000 MΩ min. (at 500 VDC) | |
| Dielectric strength * | 5,000 VAC, 50/60 Hz for 1 min between coil and contacts; 1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity |
5,000 VAC, 50/60 Hz for 1 min between coil and contacts; 3,000 VAC, 50/60 Hz for 1 min between contacts of different polarity 1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity |
| Vibration resistance | Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) Malfunction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) |
|
| Shock resistance | Destruction: 1,000 m/s2 Malfunction: 200 m/s2 when energized; 100 m/s2 when not energized |
|
| Endurance | Mechanical: AC coil: 10,000,000 operations min.; DC coil: 20,000,000 operations min. (at 18,000 operations/hr) Electrical: 100,000 operations min. (at 1,800 operations/hr under rated load) (DC coil type) |
|
| Ambient temperature | Operating: -40°C to 70°C (with no icing or condensation) | |
| Ambient humidity | Operating: 5% to 85% | |
| Weight | Approx. 20 g | |
Note: Values in the above table are the initial values.
*These values are relay only. Prease refer to the “Products Related to Common Sockets and DIN Tracks Data Sheet” for connecting sockets.
| Model | Contact form | Coil ratings | Contact ratings | Operations |
|---|---|---|---|---|
| G2R-1-S (S) | SPDT | 5 to 110 VDC 6 to 240 VAC |
10 A, 30 VDC (resistive) 10 A, 250 VAC (general use) |
100 × 103 |
| TV-3 (NO contact only) | 25 × 103 | |||
| G2R-2-S (S) | DPDT | 5 A, 30 VDC (resistive) 5 A, 250 VAC (general use) |
100 × 103 | |
| TV-3 (NO contact only) | 25 × 103 |
| Model | Contact form | Coil ratings | Contact ratings | Operations |
|---|---|---|---|---|
| G2R-1-S (S) | SPDT | 5 to 110 VDC 6 to 240 VAC |
10 A, 30 VDC (resistive) 10 A, 250 VAC (general use) |
100 × 103 |
| TV-3 (NO contact only) | 25 × 103 | |||
| G2R-2-S (S) | DPDT | 5 A, 30 VDC (resistive) 5 A, 250 VAC (general use) |
100 × 103 | |
| TV-3 (NO contact only) | 25 × 103 |
| Contact form | Coil ratings | Contact ratings | Operations |
|---|---|---|---|
| 1 pole | 6, 12, 24, 48 VDC 24, 110, 120, 230, 240 VAC |
5 A, 440 VAC (cosφ = 1.0) 10 A, 250 VAC (cosφ = 1.0) 10 A, 30 VDC (0 ms) |
100 × 103 |
| 2 poles | 6, 12, 24, 48 VDC 24, 110, 120, 230, 240 VAC |
5 A, 250 VAC (cosφ =1.0) 5 A, 30 VDC (0 ms) |
100 × 103 |
| Number of poles | Coil ratings | Contact ratings | Operations |
|---|---|---|---|
| 1 pole | 5 to 110 VDC 6 to 240 VDC |
10 A, 250 VAC (general use) 7.5 A, 250 VAC (PF0.4) 10 A, 30 VDC (resistive) 5A, 30VDC (L/R=7ms) |
100 × 103 |
| 2 poles | 5 to 110 VDC 6 to 240 VDC |
5 A, 250 VAC (general use) 2 A, 250 VAC (PF0.4) 5 A, 30 VDC (resistive) 3A, 30VDC (L/R=7ms) |
100 × 103 |
| Model | Rated carry current |
Dielectric strength | Insulation resistance* |
Remarks |
|---|---|---|---|---|
| P2RF-05-PU | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2RF-08-PU | 6 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2RFZ-05(-E) | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2RFZ-08(-E) | 6 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2RF-05 | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2RF-08 | 5 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2R-05P | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2R-08P | 5 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2R-057P | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between coil and contact terminals: 5,000 VAC for 1 min | ||||
| P2R-087P | 5 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between coil and contact terminals: 5,000 VAC for 1 min | ||||
| P2R-05A | 10 A | Between contact terminals of same polarity: 1,000 VAC for 1 min |
1,000 MΩ min. | |
| Between ground terminals: 1,500 VAC for 1 min | ||||
| Between coil and contact terminals: 4,000 VAC for 1 min | ||||
| P2R-08A | 5 A | Between contact terminals of different polarity: 3,000 VAC for 1 min |
1,000 MΩ min. | |
| Between contact terminals of same polarity: 1,000 VAC for 1 min |
||||
| Between ground terminals: 1,500 VAC for 1 min | ||||
| Between coil and contact terminals: 4,000 VAC for 1 min |