• Realized about 25% lower profile than conventional products, contributing to further miniaturization of the control panel.
• Realized opening and closing ability with one pole 6 A slim shape.
• Micro load products for one pole 50 mA using Au-plated contacts for small load switching also available.
• Since G2RV is a transparent case, confirming the state of the contact with the naked eye is possible, and easy to confirm abnormality on-site (installed location).
• Screw terminal is also stocked to meet the screw type needs.
• Mounted relay uses plug-in terminals that are difficult to bend when exchanging.
• G3RV-SR featuring a solid state relay similar in shape to G2RV-SR also available.
• Coil surge absorption circuit is equipped as standard.
Rated input voltage |
Rated current | Must operate voltage |
Must release voltage |
Power consumption | Maximum allowable voltage |
|||
---|---|---|---|---|---|---|---|---|
AC | DC | Percentage of the rated voltage |
AC (VA) | DC (mW) | Percentage of the rated voltage |
|||
50 Hz | 60 Hz | |||||||
12 VDC | – | – | 27.9 mA | 80% max.* | 10% min. | – | Approx. 300 mW | 110% |
24 VDC | – | – | 13.5 mA | – | Approx. 300 mW | |||
24 VAC/VDC | 12.5 mA | 12.6 mA | 12.6 mA | Approx. 0.5 VA | Approx. 300 mW | |||
48 VAC/VDC | 5.9 mA | 6.1 mA | 5.2 mA | Approx. 0.4 VA | Approx. 250 mW | |||
100 VAC | 5.9 mA | 6.0 mA | – | Approx. 0.8 VA | – | |||
110 VAC | 5.9 mA | 5.9 mA | – | Approx. 0.8 VA | – | |||
200 VAC | 6.6 mA | 7.6 mA | – | Approx. 1.7 VA | – | |||
230 VAC | 7.3 mA | 8.4 mA | – | Approx. 1.7 VA | – |
Item | Standard (G2RV-SR700, 500, 701, 501) |
For microloads (G2RV-SR700-AP, 500-AP) *2 |
|
---|---|---|---|
Contact configuration | SPDT | ||
Load | Resistive load (cosφ=1) |
Inductive load (cosφ=0.4, L/R=7ms) |
Resistive load (cosφ=1) |
Rated load | 6 A at 250 VAC 6 A at 30 VDC |
2.5 A at 250 VAC 2 A at 30 VDC |
50 mA at 30 VAC 50 mA at 36 VDC |
Rated carry current | 6 A | 50 mA | |
Maximum switching voltage | 440 VAC, 125 VDC | 30 VAC, 36 VDC | |
Maximum switching current | 6 A | 50 mA | |
Maximum switching power | 1,500 VA 180 W |
500 VA 60 W |
– |
Failure rate P value (reference value) *1 |
10 mA at 5 VDC | 1 mA at 100 mVDC |
*1. P level: λ60=0.1×10-6/times
This value is the value in switching frequency 120 operations/min.
*2. If the Au plating layer is destroyed, the number will be the same as the standard type.
Item | Standard (G2RV-SR700, 500, 701, 501) |
For microloads (G2RV-SR700-AP, 500-AP) |
|
---|---|---|---|
Contact resistance *1 | 100 mΩ max. | ||
Operate (Set) time *1 | 20 ms max. | ||
Release time *1 | AC, AC/DC: 40 ms max. DC: 20 ms max. |
||
Maximum operating frequency |
Mechanical: 18,000 operations/h Electrical: 1,800 operations/h (rated load) |
||
Insulation resistance | 1,000 MΩ min. (at 500 VDC) | ||
Dielectric strength | Between coil and contacts: 4,000VAC 50/60 Hz 1 min Contact between the same polarity: 1,000 VAC 50/60 Hz 1 min |
||
Vibration resistance *2 | Destruction: 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) Malfunction: 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) |
||
Shock resistance *2 | Destruction: 1,000 m/s2 Malfunction: Energized 200m/s2, Non-energized 100m/s2 |
||
Endurance *1 | Mechanical | 5,000,000 operations min. | |
Electrical | NO contact: 70,000 operations min. NC contact: 50,000 operations min. |
5,000,000 operations min. | |
Ambient operating temperature |
Operating: -40 to +55°C (with no icing or condensation) | ||
Ambient operating humidity |
Operating: 5 to 85% RH | ||
Weight | Approx. 30 g | ||
Contact material | Ag alloy | Ag alloy + Au plating |
Note: Above values are initial values.
*1. Value is at ambient temperature of 23°C.
*2. Value when the end plate is used.
Model | Contact form | Operation coil ratings | Contact ratings | Operations |
---|---|---|---|---|
G2RV-SR series | SPDT | 12 to 48 VDC 24 to 230 VAC |
6 A at 250 VAC (Resistive load) 6 A at 30 VDC (Resistive load) 2 A at 400 VAC (Resistive load)* |
6,000 |
* If the load voltage exceeds 250 VAC, please attach with a spacing of 12 mm min., or use a separate plate (XW5Z-EP12).
Model | Contact form | Operation coil ratings | Contact ratings | Operations |
---|---|---|---|---|
G2RV-SR series | SPDT | 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC |
6 A at 250 VAC (Resistive load) 6 A at 30 VDC (Resistive load) 2 A at 400 VAC (Resistive load)* |
50,000 50,000 6,000 |
* If the load voltage exceeds 250 VAC, please attach with a spacing of 12 mm min., or use a separate plate (XW5Z-EP12).
Model | Contact form | Operation coil ratings | Contact ratings |
---|---|---|---|
G2RV-SR500 G2RV-SR700 |
SPDT | 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC |
6 A at 250 VAC (Resistive load) |
2.5 A at 250 VAC (PF0.4) | |||
6 A at 30 VAC (Ress) | |||
2 A at 30 VDC (L/R=7ms) | |||
G2RV-SR501 G2RV-SR701 |
SPDT | 12, 24 VDC 24 VAC/VDC |
6 A at 250 VAC (Resistive load) |
2.5 A at 250 VAC (PF0.4) | |||
6 A at 30 VAC (Ress) | |||
2 A at 30 VDC (L/R=7ms) | |||
G2RV-SR500-AP G2RV-SR700-AP |
SPDT | 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC |
0.05 A at 30 VAC (Resistive load) 0.05 A at 36 VDC (Resistive load) |