Floatless Level Switch (Plug-in Type) 61F-G[]P

• Large switching capacity: 5 A at 220 VAC (resistive load).

• Easy to handle with DIN rail mounting.

• Replace for maintenance without rewiring the socket.

Item General-purpose
Controller
61F-G1P
61F-G2P
61F-IP
Long-distance
Controllers
61F-G1PL
61F-G2PL
61F-IPL
*2
High-sensitivity
Controllers
61F-G1PH
61F-G2PH
61F-IPH
*1, *6
Low-sensitivity
Controller
61F-G1PD
61F-G2PD
61F-IPD
Controlling materials
and operating
conditions
For control of
ordinary purified
water or sewage
water
For control of ordinary
purified water in cases where
the distance between sewage
pumps and water tanks or
between receiver tanks and
supply tanks is long or where
remote control is required.
For control of
liquids with high
specific resistance
such as distilled
water
For control of liquids
with low specific
resistance such as
salt water, sewage
water, acid
chemicals, alkali
chemicals
Supply voltage 100, 200, 220 VAC; 50/60 Hz
Operating voltage
range
85% to 110% of rated voltage
Interelectrode
voltage
8 VAC 24 VAC 8 VAC
Interelectrode
current
Approx. 1 mA AC max. Approx. 0.4 mA AC
max.
Approx. 1.2 mA AC
max.
Power consumption Approx. 6.4 VA max.
Interelectrode
operate resistance
0 to approx. 4 kΩ 0 to 1.8 kΩ (for 2 km)
0 to 0.7 kΩ (for 4 km)
Approx. 15 kΩ to
approx. 70 kΩ *5
0 to approx. 1.8 kΩ
Interelectrode
release resistance
Approx. 15 k to
∞ Ω
4 k to ∞ Ω (for 2 km)
2.5 k to ∞ Ω (for 4 km)
Approx. 300 k to
∞ Ω
Approx. 5 k to ∞ Ω
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length *3 1 km max. 2 km max.
4 km max.
50 m max. 1 km max.
Control output 2 A, 200 VAC (Inductive load: cosφ = 0.4)
5 A, 200 VAC (Resistive load)
Ambient temperature Operating: -10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resistance
*4
100 MΩ min. (at 500 VDC)
Dielectric strength
*4
2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Weight Approx. 495 g