• Compact: 49.4 × 38 × 84 mm (H×W×D).
• Easy identification of operating status with LED operation indicator.
• Independent DPDT contacts on 11-Pin Models.
• CE marking and UL/CSA compliance.
Item | General-purpose Controller 61F-GP-N |
High-temperature Controller 61F-GP-NT |
Long-distance Controllers 61F-GP-NL 2KM (for 2 km) 61F-GP-NL 4KM (for 4 km) |
---|---|---|---|
Controlling materials and operating conditions |
For control of ordinary purified water or sewage water |
For control of ordinary purified water or sewage where operating ambient temperature is high. |
For control of ordinary purified water in cases where the distance between sewage pumps and water tanks or between receiver tanks and supply tanks is long or where remote control is required. |
Supply voltage | 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz | ||
Operating voltage range | 85% to 110% of rated voltage | ||
Interelectrode voltage | 8 VAC | ||
Interelectrode current | Approx. 1 mA AC max. | ||
Power consumption | Approx. 3.5 VA max. | ||
Interelectrode operate resistance |
0 to approx. 4 kΩ | 0 to approx. 4 kΩ | 0 to approx. 1.3 kΩ (for 2 km) 0 to approx. 0.5 kΩ (for 4 km) |
Interelectrode release resistance |
Approx. 15 k to ∞ Ω | Approx. 15 k to ∞ Ω | 4 k to ∞ Ω (for 2 km) 2.5 k to ∞ Ω (for 4 km) |
Response time | Operate:80 ms max. Release:160 ms max. |
||
Cable length *1 | 1 km max. | 600 m max. | 2 km max. 4 km max. |
Control output | 1 A, 250 VAC (Inductive load: cosφ = 0.4) 3 A, 250 VAC (Resistive load) |
||
Ambient temperature | Operating:-10 to 55°C (-10 to 70°C for high-temperature controller) | ||
Ambient humidity | Operating:45% to 85% RH | ||
Insulation resistance *2 |
100 MΩ min. (at 500 VDC) | ||
Dielectric strength *2 | 2000 VAC, 50/60 Hz for 1 min. | ||
Life expectancy | Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. |
||
Weight | Approx. 155 g | ||
Accessories | Hold-down clip PFC-N8 | ||
Approved standards | UL508, CSA C22.2 No.14, EN61010-1, EN61326-1 Industrial electromagnetic environment |
Item | High-sensitivity Controller 61F-GP-NH *4 |
Low-sensitivity Controller 61F-GP-ND |
Two-wire Controller 61F-GP-NR |
---|---|---|---|
Controlling materials and operating conditions |
For control of liquids with high specific resistance such as distilled water |
For control of liquids with low specific resistance such as salt water, sewage water, acid chemicals, alkali chemicals |
For control of ordinary purified water or sewage water used in combination with Two-wire Electrode Holder (incorporating a resistor of 6.8 kΩ) |
Supply voltage | 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz | ||
Operating voltage range | 85% to 110% of rated voltage | ||
Interelectrode voltage | 8 VAC | ||
Interelectrode current | Approx. 0.12 mA AC max. | Approx. 1 mA AC max. | |
Power consumption | Approx. 3.5 VA max. | ||
Interelectrode operate resistance |
Approx. 10 kΩ to approx. 40 kΩ *3 |
0 to approx. 1.3 kΩ | 0 to approx. 2 kΩ |
Interelectrode release resistance |
Approx. 100 k to ∞ Ω | Approx. 4 k to ∞ Ω | Approx. 15 k to ∞ Ω |
Response time | Operate:80 ms max. Release:160 ms max. |
||
Cable length *1 | 50 m max. | 1 km max. | 800 m max. |
Control output | 1 A, 250 VAC (Inductive load: cosφ = 0.4) 3 A, 250 VAC (Resistive load) |
||
Ambient temperature | Operating:-10 to 55°C (-10 to 70°C for high-temperature controller) | ||
Ambient humidity | Operating:45% to 85% RH | ||
Insulation resistance *2 | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength *2 | 2000 VAC, 50/60 Hz for 1 min. | ||
Life expectancy | Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. |
||
Weight | Approx. 155 g | ||
Accessories | Hold-down clip PFC-N8 | ||
Approved standards | UL508, CSA C22.2 No.14, EN61010-1, EN61326-1 Industrial electromagnetic environment |
Item | General-purpose Controller 61F-GP-N8 61F-GP-N8Y *4 |
Long-distance Controllers 61F-GP-N8L 2KM (for 2 km) 61F-GP-N8L 4KM (for 4 km) |
High-sensitivity Controllers 61F-GP-N8H 61F-GP-N8HY *4 |
---|---|---|---|
Controlling materials and operating conditions |
For control of ordinary purified water or sewage water |
For control of ordinary purified water in cases where the distance between sewage pumps and water tanks or between receiver tanks and supply tanks is long or where remote control is required. |
For control of liquids with high specific resistance such as distilled water |
Supply voltage | 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz | ||
Operating voltage range | 85% to 110% of rated voltage | ||
Interelectrode voltage | 8 VAC | 24 VAC | |
Interelectrode current | Approx. 1 mA AC max. | Approx. 0.4 mA AC max. | |
Power consumption | Approx. 3.5 VA max. | ||
Interelectrode operate resistance |
0 to approx. 4 kΩ | 0 to 1.3 kΩ (for 2 km) 0 to 0.5 kΩ (for 4 km) |
Approx. 15 kΩ to approx. 70 kΩ *3 |
Interelectrode release resistance |
Approx. 15 k to ∞ Ω | 4 k to ∞ Ω (for 2 km) 2.5 k to ∞ Ω (for 4 km) |
Approx. 300 k to ∞ Ω |
Response time | Operate: 80 ms max. Release: 160 ms max. |
||
Cable length *1 | 1 km max. | 2 km max. 4 km max. |
50 m max. |
Control output | 1 A, 250 VAC (Inductive load: cosφ = 0.4) 3 A, 250 VAC (Resistive load) |
||
Ambient temperature | Operating: -10 to 55°C | ||
Ambient humidity | Operating: 45% to 85% RH | ||
Insulation resistance *2 | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength *2 | 2000 VAC, 50/60 Hz for 1 min. | ||
Life expectancy | Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. |
||
Weight | Approx. 155 g | ||
Accessories | Hold-down clip PFC-N8 | ||
Approved standards | UL508, CSA C22.2 No.14, EN61010-1, EN61326-1 Industrial electromagnetic environment |
Item | Low-sensitivity Controller 61F-GP-N8D |
Two-wire Controller 61F-GP-N8R |
Variable Sensitivity Controller 61F-GP-N8-V50 |
---|---|---|---|
Controlling materials and operating conditions |
For control of liquids with low specific resistance such as salt water, sewage water, acid chemicals, alkali chemicals |
For control of ordinary purified water or sewage water used in combination with Two-wire Electrode Holder (incorporating a resistor of 6.8 kΩ) |
For control of cases where variable sensitivity control is required such as detection of froth on the surface of a liquid, control of soil moisture content, or detection of degree of water pollution |
Supply voltage | 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz |
24, 110, 220 or 240 VAC; 50/60 Hz | |
Operating voltage range | 85% to 110% of rated voltage | ||
Interelectrode voltage | 8 VAC | 24 VAC | |
Interelectrode current | Approx. 1 mA AC max. | Approx. 3 mA AC max. | |
Power consumption | Approx. 3.5 VA max. | ||
Interelectrode operate resistance |
0 to approx. 1.3 kΩ | 0 to approx. 2 kΩ | 0 to 50 kΩ (Variable) |
Interelectrode release resistance |
Approx. 4 k to ∞ Ω | Approx. 15 k to ∞ Ω | Operating resistance +50 kΩ max. |
Response time | Operate: 80 ms max. Release: 160 ms max. |
||
Cable length *1 | 1 km max. | 800 m max. | 50 m max. |
Control output | 1 A, 250 VAC (Inductive load: cosφ = 0.4) 3 A, 250 VAC (Resistive load) |
||
Ambient temperature | Operating: -10 to 55°C | ||
Ambient humidity | Operating: 45% to 85% RH | ||
Insulation resistance *2 | 100 MΩ min. (at 500 VDC) | ||
Dielectric strength *2 | 2000 VAC, 50/60 Hz for 1 min. | ||
Life expectancy | Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. |
||
Weight | Approx. 155 g | ||
Accessories | Hold-down clip PFC-N8 | ||
Approved standards | UL508, CSA C22.2 No.14, EN61010-1, EN61326-1 Industrial electromagnetic environment |