• Wide time range from 1/100 seconds to 9999 hrs.
• Built-in power supply incorporated in timer enables direct connection of sensors and other components.
• Draw-out construction allows maintenance without disconnecting the wiring.
• Power supply freely selectable within a range of 100 to 240 VAC; a DC-operated version is also available.
• Control outputs of both contact type and transistor type simultaneously available.
• Seven operating modes (N, F, C, R, K, P, and Q) are available.
Item | H5AN-4D/H5AN-4DM |
---|---|
Rated supply voltage | H5AN-4D: 100 to 240 VAC (50/60 Hz), 12 to 24, 48, or 100 VDC (permissible ripple: 20% max.) H5AN-4DM: 100 to 240 VAC (50/60 Hz), 12 to 24 VDC (permissible ripple: 20% max.) |
Operating voltage range |
85% to 110% of rated supply voltage |
Power consumption | Approx. 10 VA (at 240 VAC), approx. 5 W (at 24 VDC) |
Resetting system and gate input |
Reset by power-OFF: min. power OFF time: 0.5 s * External reset or gate (common to contact and transistor inputs): min. reset input signal width: 0.02 s |
One-shot output time | 0.1 to 1 s (adjustable) |
Control outputs | Contact output: SPDT, 3 A at 250 VAC, resistive load (cosφ = 1) Transistor output: Open collector, 100 mA max. at 30 VDC max. |
Power supply for externally connected components |
12 VDC±10%, 80 mA (permissible ripple: 5% max.) |
Case color | Light gray (Munsell 5Y7/1) |
* This does not apply to to the models ending with -M when memory backup is enabled.
Accuracy of operating time | ±0.01% ±0.05 s max. (power OFF start), ±0.005% ±0.03 s max. (reset start) *1 |
---|---|
Setting error | |
Influence of voltage | |
Influence of temperature | |
Insulation resistance | 100 MΩ min. (at 500 VDC) (between current-carrying terminal and exposed non- current carrying metal parts, between non-continuous contacts) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying metal parts) 750 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Impulse withstand voltage | 6 kV (between power supply terminal) 6 kV (between current-carrying terminal and exposed non-current carrying metal parts) |
Vibration resistance | Destruction: 10 to 55 Hz with 0.75-mm double amplitude Malfunction: 10 to 55 Hz with 0.5-mm double amplitude |
Shock resistance | Destruction: 300 m/s2 (approx. 30G) Malfunction: 100 m/s2 (approx. 10G) |
Ambient temperature | Operating: -10°C to 55°C Storage: -25°C to 65°C |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load) |
Degree of protection | IP-30 |
Memory backup storage method *2 |
Non-volatile memory (Number of writes: 1 million times, Data retention: 10 years) |
Weight | Approx. 360 g |
Approved safety standards | UL508/CSA C22.2 No. 14 conforms to EN61812-1 (Pollution degree 2/overvoltage category III) CCC: GB/T 14048.5 Pollution degree 2, Overvoltage category III * |
---|---|
EMC | (EMI) EN61812-1 Emission Enclosure: EN55011 Group 1 class A Emission AC mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Voltage Dip/Interruption:IEC61000-4-11 |
* CCC certification requirements.
Recommended fuse | Contact Output: 021602.5 (250 VAC, 2.5 A), manufactured by Littelfuse Transistor Output: 0216.100 (250 VAC, 100 mA) manufactured by Littelfuse |
---|---|
Rated operating voltage Ue Rated operating current Ie |
Contact Output: AC-15: Ue: 250 VAC, Ie: 3 A DC-13: Ue: 30 VDC, Ie: 0.5 A Transistor Output: DC-13: Ue: 30 VDC, Ie: 0.1 A |
Rated insulation voltage | 250 V |
Rated impulse withstand voltage (altitude: 2,000 m max.) |
4 kV (at 240 VAC) |
Conditional short-circuit current | 1,000 A |