• Slim design with a width of only 17 mm (three-contact models).
• Reversible design allowing either front or rear mounting.
• Built-in Switches with two- or three-terminal contact construction are available.
• Operation Key with rubber mounting hole to absorb vibration and shock.
• IP67 degree of protection.
• Machinery Directive
• Low Voltage Directive
• EN ISO 14119
• EN60204-1
• GS-ET-15
| Certification body | Standard | File No. |
|---|---|---|
| TÜV SÜD | EN60947-5-1 (certified direct opening) |
Consult your OMRON representative for details. |
| UL * | UL508 CSA C22.2 No. 14 |
E76675 |
| CQC (CCC) | GB/T 14048.5 | Consult your OMRON representative for details. |
* Certification for CSA C22.2 No. 14 is authorized by the UL mark.
| Utilization category | AC-15 | DC-13 |
|---|---|---|
| Rated operating current (Ie) | 0.75 A | 0.27 A |
| Rated operating voltage (Ue) | 240 V | 250 V |
Note: Use a 10 A fuse type gI or gG that conforms to IEC60269 as a short-circuit protection device.
| Rated voltage | Carry current | Current (A) | Volt-amperes (VA) | ||
|---|---|---|---|---|---|
| Make | Break | Make | Break | ||
| 120 VAC | 2.5 A | 15 | 1.5 | 1,800 | 180 |
| 240 VAC | 7.5 | 0.75 | |||
| Rated voltage | Carry current | Current (A) | Volt-amperes (VA) | ||
|---|---|---|---|---|---|
| Make | Break | Make | Break | ||
| 125 VDC | 2.5 A | 0.55 | 0.55 | 69 | 69 |
| 250 VDC | 0.27 | 0.27 | |||
| Interlock type | Type 2 (EN ISO 14119) | |
|---|---|---|
| Coding level | Low level coded (EN ISO 14119) | |
| Degree of protection *1 | IP67 (EN60947-5-1) | |
| Durability *2 | Mechanical | 1,000,000 operations min. |
| Electrical | 100,000 operations min. (1 A resistive load at 125 VAC) *3 | |
| Operating speed | 0.1 to 0.5 m/s | |
| Operating frequency | 30 operations/minute max. | |
| Direct opening force *4 | 60 N min. | |
| Direct opening travel *4 | 10 mm min. | |
| Contact resistance | 300 mΩ max. (with 1 m cable) 500 mΩ max. (with 3 m cable) 700 mΩ max. (with 5 m cable) |
|
| Minimum applicable load *5 | Resistive load of 4 mA at 24 VDC (N-level reference value) | |
| Rated insulation voltage (Ui) | 250 V | |
| Rated frequency | 50/60 Hz | |
| Protection against electric shock | Class II (double insulation) ![]() |
|
| Pollution degree (operating environment) | 3 (EN60947-5-1) | |
| Impulse withstand voltage (Uimp) (EN60947-5-1) |
Between terminals of same polarity | 2.5 kV |
| Between terminals of different polarity |
4 kV | |
| Between each terminal and non- current carrying metallic parts |
6 kV | |
| Insulation resistance | 100 MΩ min. (at 500 VDC) between terminals of the same polarities, between terminals of different polarities, and between each terminal and non-current carrying metal parts |
|
| Contact gap | 2 × 2 mm min. | |
| Vibration resistance | Malfunction | 10 to 55 Hz, 0.35 mm single amplitude |
| Shock resistance | Destruction | 1,000 m/s2 min. |
| Malfunction | 300 m/s2 min. | |
| Conditional short-circuit current | 100 A (EN60947-5-1) | |
| Conventional free air thermal current (Ith) | 2.5 A (EN60947-5-1) | |
| Ambient operating temperature | -30 to 70°C (with no icing) | |
| Ambient operating humidity | 95% max. | |
| Cable | UL2464 No. 22 AWG, finishing O.D.: 7.2 mm | |
| Weight | Approx. 120 g (D4GS-N1R, with 1 m cable) | |